Install a Fan Module
Caution -
Electrical hazard. During a hot-service procedure, voltage is present. Do not reach
into the vacant fan module slot with your hand or any object. Do not touch the exposed CMOD
fan module power connector.
When the fan is removed from the slot, a hinged air vane drops down to close the slot. The vane
maintains system cooling and prevents a disruption of server airflow during hot service.
Caution -
Server overtemperature. The slot's air vane maintains system cooling by preventing a
disruption of server airflow. Do not open the air vane when the system is running.
Related Information
■
“Remove a Fan Frame” on page 136
■
“Install a Fan Module” on page 133
Install a Fan Module
Use this procedure after removing a fan module to install a replacement fan module or to install
a fan module after accessing the CMODs behind it.
Servicing Components
133