11 Troubleshooting
11-20
NJ-series CPU Unit Motion Control User’s Manual (W507)
Error Descriptions
Event name
User Program/Controller Configurations and Setup Trans-
fer Error
Event code
10200000 hex
Meaning
The user program or Controller Configurations and Setup were not transferred correctly.
Source
PLC Function Module
Motion Control Function Module
EtherCAT Master Function Module
EtherNet/IP Function Module
Source details
None
Detection
timing
At power ON or
Controller reset
Error attributes
Level
Major fault
Recovery
Cycle the power
supply or reset
the Controller.
Log category
System
Effects
User program
Stops.
Operation
All outputs are stopped.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The user program or Controller Con-
figurations and Setup are not correct
because the power supply to the Con-
troller was interrupted or communica-
tions with the Sysmac Studio were
disconnected during a download of
the user program or the Controller
Configurations and Setup.
Clear all of memory and then down-
load the project from the Sysmac Stu-
dio. If attached information is
registered, cycle the power supply to
the Controller and then implement the
above correction.
Do not turn OFF the power supply to
the Controller or disconnect commu-
nications with the Sysmac Studio dur-
ing a download of the user program or
the Controller Configurations and
Setup.
The user program or Controller Con-
figurations and Setup are not correct
because the power supply to the Con-
troller was interrupted during online
editing.
Do not interrupt the power supply to
the Controller during online editing.
The user program or Controller Con-
figurations and Setup are not correct
because the power supply to the Con-
troller was interrupted during a Clear
All Memory operation.
Do not interrupt the power supply to
the Controller during a Clear All Mem-
ory operation.
Non-volatile memory failed.
If the error persists even after you
make the above correction, replace
the CPU Unit.
None
Attached
information
Attached Information 1: Cause Details
None: Power was interrupted or communications were disconnected during a download or power was interrupted dur-
ing online editing.
Downloading/Predownloading: For other causes, the timing of error occurrence (during download or during download
preparations) is given.
Precautions/
Remarks
None
Summary of Contents for NJ501-1300
Page 12: ...Sections in this Manual 10 NJ series CPU Unit Motion Control User s Manual W507...
Page 18: ...16 NJ series CPU Unit Motion Control User s Manual W507 CONTENTS...
Page 22: ...Read and Understand this Manual 20 NJ series CPU Unit Motion Control User s Manual W507...
Page 34: ...Revision History 32 NJ series CPU Unit Motion Control User s Manual W507...
Page 86: ...3 Configuring Axes and Axes Groups 3 28 NJ series CPU Unit Motion Control User s Manual W507...
Page 122: ...5 Motion Control Parameters 5 24 NJ series CPU Unit Motion Control User s Manual W507...
Page 158: ...6 Motion Control Programming 6 36 NJ series CPU Unit Motion Control User s Manual W507...
Page 166: ...7 Manual Operation 7 8 NJ series CPU Unit Motion Control User s Manual W507...
Page 182: ...8 Homing 8 16 NJ series CPU Unit Motion Control User s Manual W507...
Page 346: ...10 Sample Programming 10 92 NJ series CPU Unit Motion Control User s Manual W507...
Page 422: ...Appendices A 18 NJ series CPU Unit Motion Control User s Manual W507...
Page 423: ...Index 1 NJ series CPU Unit Motion Control User s Manual W507 I Index...
Page 430: ...Index 8 NJ series CPU Unit Motion Control User s Manual W507 Index...