6 Parameters
6 - 40
E5@C Digital Temperature Controllers User’s Manual (H174)
PV/MV (Manual MV)
• The manual control level display appears as shown below.
E5EC/E5AC
E5CC/E5CC-U/E5DC
*
When the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV lower
limit to the MV upper limit.
z
Related Parameters
Standard or Heating/Cooling (Initial Setting Level): Page 6-45
Function
100
50.0
25
PV/SP/Manual MV
50.0
25
PV/Manual MV
Monitor range
Unit
Process value
Temperature: According to indication range for each sensor.
Analog: Scaling lower limit
−
5% FS to Scaling upper limit +5% FS
(Refer to A-7 Sensor Input Setting Range, Indication Range, Con-
trol Range.)
EU
Set point
SP lower limit to SP upper limit
EU
Setting range
Unit
MV (Manual MV)
Standard control
Position-proportional control
−
5.0 to 105.0*
%
Heating/cooling control
−
105.0 to 105.0*
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...