A Appendices
A - 24
E5@C Digital Temperature Controllers User’s Manual (H174)
*2
*2.1
Initialized when the transfer output type is changed.
Initialized if the input type, temperature unit, scaling upper/lower limit, or SP upper/lower limit is changed
when the transfer output type is SP, ramp SP, or PV.
(When initialized by the initializing settings, it is initialized to 100.0/0.0.)
*3
PRST (Program Start) can be set even when the Program Pattern parameter is set to OFF, but the
function will be disabled.
*4
This function can be set for heating/cooling control or for floating control for Position-proportional Models,
but the setting will be disabled.
*1
When the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV lower limit to the MV upper
limit.
*2
The valve opening is monitored for floating control or for close control with the Direct Setting of Position-proportional MV
parameter set to OFF.
The contents displayed vary depending on the Monitor/Setting 1 to 5 (advanced function setting
level) setting.
Transfer output type
Setting (monitor) range
Default*4.1
(transfer output upper/lower
limits)
Unit
Set Point
SP lower limit to SP upper limit
SP upper limit/lower limit
EU
Set Point During SP
Ramp
SP lower limit to SP upper limit
SP upper limit/lower limit
EU
PV
Temperature input: Input setting range lower
limit to Input setting range upper limit
Input setting range upper/lower
limit
EU
Analog input: Scaling lower limit to Scaling
upper limit
Scaling upper/lower limit
MV (Heating)
Standard:
−
5.0 to 105.0
Heating/cooling: 0.0 to 105.0
100.0/0.0
%
MV (Cooling)
0.0 to 105.0
100.0/0.0
%
Valve opening
−
10.0 to 110.0
100.0/0.0
%
A-6-4
Manual Control Level
Parameters
Setting (monitor) value
Default
Unit
Manual MV
−
5.0 to 105.0 (standard)
*1
−
105.0 to 105.0 (heating/cooling)
*2
−
5.0 to 105.0 (position-proportional)
*1*2
0.0
%
A-6-5
Monitor/Setting Item Level
A-6-6
Advanced Function Setting Level
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
Parameter Initialization
init
OFF, FACT
off
,
fact
OFF
None
Number of Multi-SP
Points
mspu
OFF(1), 2 to 8
off
,
2
to
8
OFF
None
SP Ramp Time Unit
spru
S: EU/second
M: EU/minute
H: EU/hour
s
,
m
,
h
M
None
Standby Sequence
Reset
rest
Condition A, condition B
a
,
b
Condition A
None
Auxiliary Output 1
Open in Alarm
sb1n
N-O: Close in alarm
N-C: Open in alarm
n-o
,
n-c
N-O
None
Auxiliary Output 2
Open in Alarm
sb2n
N-O: Close in alarm
N-C: Open in alarm
n-o
,
n-c
N-O
None
Auxiliary Output 3
Open in Alarm
sb3n
N-O: Close in alarm
N-C: Open in alarm
n-o
,
n-c
N-O
None
Auxiliary Output 4
Open in Alarm
sb4n
N-O: Close in alarm
N-C: Open in alarm
n-o
,
n-c
N-O
None
HB ON/OFF
hbu
OFF, ON
off
,
on
ON
None
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...