5 Advanced Operations
5 - 50
E5@C Digital Temperature Controllers User’s Manual (H174)
This procedure sets the MV change rate limit to 5.0%/s. The related
parameters are as follows:
PID ON/OFF = PID
ST = OFF
Operating Procedure
• Setting 2-PID Control
1
Press the
M
Key several times in the Initial Setting Level to
display
cntl
(PID ON/OFF).
Initial Setting Level
2
Press the
U
or
D
Key to select
pid
(PID).
The default is
onof
(ON/OFF control).
• Turning OFF Self-tuning
1
Press the
M
Key several times in the Initial Setting Level to
display
st
(ST: self-tuning).
Initial Setting Level
2
Press the
U
or
D
Key to set the value to
off
.
The default is
on
.
• Setting the MV Change Rate Limit
1
Press the
M
Key several times in the Adjustment Level to dis-
play
orl
(MV Change Rate Limit).
Adjustment Level
2
Press the
U
or
D
Key to set the value to 5.0.
The default is 0.0 (%/s).
onof
cntl
PID ON/OFF
pid
cntl
on
st
ST
off
st
0.0
orl
MV Change
Rate Limit
5.0
orl
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...