6 - 29
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-4 Ad
justm
ent Le
v
el
6
*
The unit is determined by the setting of the Integral/Derivative Time Unit parameter. The
Proportional Band, Integral Time, and Derivative Time parameters are initialized if the
Integral/Derivative Time Unit parameter is changed.
z
Related Parameters
AT Execute/Cancel (Adjustment Level): Page 6-20
Integral/Derivative Time Unit (Advanced Function Setting Level): Page 6-65
c-p
Proportional Band (Cooling)
The control must be set to heating/cooling control
and 2-PID control.
c-i
Integral Time (Cooling)
c-d
Derivative Time (Cooling)
These parameters set the PID constants for cooling control. These parameters are automat-
ically set according to the Heating/Cooling Tuning Method parameter when AT or ST is exe-
cuted.
*
The unit is determined by the setting of the Integral/Derivative Time Unit parameter. The
Proportional Band (Cooling), Integral Time (Cooling), and Derivative Time (Cooling)
parameters are initialized if the Integral/Derivative Time Unit parameter is changed.
z
Related Parameters
AT Execute/Cancel (Adjustment Level): Page 6-20
Integral/Derivative Time Unit (Advanced Function Setting Level): Page 6-65
Setting
Parameter
Setting range
Unit
Default
Proportional
Band
Temperature input
0.1 to 999.9
°
C or
°
F
8.0
Analog input
%FS
10.0
Integral Time * Integral/
Derivative
Time Unit of
1 s
Standard, heating/cooling, or
close position-proportional
control
0 to 9999
Seconds
233
Floating position-proportional
control
1 to 9999
Integral/
Derivative
Time Unit of
0.1 s
Standard, heating/cooling, or
close position-proportional
control
0.0 to 999.9
Seconds
233.0
Floating position-proportional
control
0.1 to 999.9
Derivative
Time *
Integral/Derivative Time Unit of 1 s
0 to 9999
Seconds
40
Integral/Derivative Time Unit of 0.1 s
0.0 to 999.9
Seconds
40.0
See
See
Function
Setting
Parameter
Setting range
Unit
Default
Proportional Band
(Cooling)
Temperature input
0.1 to 999.9
°
C or
°
F
8.0
Analog input
%FS
10.0
Integral Time
(Cooling) *
Integral/Derivative
Time Unit of 1 s
0 to 9999
Seconds
233
Integral/Derivative
Time Unit of 0.1 s
0.0 to 999.9
Seconds
233.0
Derivative Time
(Cooling)*
Integral/Derivative
Time Unit of 1 s
0 to 9999
Seconds
40
Integral/Derivative
Time Unit of 0.1 s
0.0 to 999.9
Seconds
40.0
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...