5 Advanced Operations
5 - 66
E5@C Digital Temperature Controllers User’s Manual (H174)
2. The Logic Operation Editor
will be displayed. Confirm
that the screen for work bit 1
is displayed, and select
Operation 3 from the
Operation Type Field.
3.
Set the operation by
selecting one of the
following:
Work bit 1 input assignment
A = 4: Event input 2
(external input)
Work bit 1 input assignment
B = 0: Always OFF
Work bit 1 input assignment
C = 0: Always OFF
Work bit 1 input assignment
D = 0: Always OFF
4. Invert work bit 1. Click
(Normally open) to change it
to
(Normally closed).
5. Assign RUN/STOP to event
input 2. Set “5: Work bit 1”
for the event input data for
event input 2, and set
“RUN/STOP” for the
assignment function.
6. Closing the Logic Operation
Editor Dialog Box
Click the Close Button.
This completes the
procedure for setting
parameters using the
CX-Thermo. Transfer the
settings to the Controller to
set the Controller. Refer to
CX-Thermo help for the
procedure to transfer the
settings.
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...