2 Preparations
2 - 6
E5@C Digital Temperature Controllers User’s Manual (H174)
z
E5DC
• The E5CC-U and E5DC cannot be waterproofed.
• Waterproofing is not possible when group mounting several Controllers.
• The recommended panel thickness is 1 to 5 mm for the E5CC and E5CC-U, and 1 to 8 mm for E5EC,
E5AC, and E5DC.
• Controllers must not be closely mounted vertically. (Observe the recommended mounting space
limits.)
• When two or more Digital Controllers are mounted, make sure that the surrounding temperature does
not exceed the allowable operating temperature specified in the specifications.
*
For E5EC models with two control outputs (QQ, QR, CQ, RR, CC, or PR) and 011, 012, 013, or 014 options
(shown below), the ambient temperature for group mounting must be 45
°
C max.
To mount these models at an ambient temperature of 55
°
C, install them at the following intervals.
120 min.
Individual Mounting
Two-Unit Mounting
Group Mounting
22.7
+0.3
0
45
+0.6
0
92
+0.8
0
92
+0.8
0
92
+0.8
0
(22.5 x number of Units)
+1.0
0
E5EC-
@@
@
@
@
M-
@@@
QQ, QR,
RR, CC, CQ, PR
011, 012,
013, 014
45
+0.6
0
92
120 min.
+0.8
0
60 min.
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...