A - 25
A Appendices
E5@C Digital Temperature Controllers User’s Manual (H174)
A
-6 P
aram
eter Operation L
ists
A
A-6-6 Adv
anced F
unct
ion Setting Le
v
el
Heater Burnout Latch
hbl
OFF, ON
off
,
on
OFF
None
Heater Burnout
Hysteresis
hbh
0.1 to 50.0
0.1
A
ST Stable Range
st-b
0.1 to 999.9
15.0
°
C or
°
F
α
alfa
0.00 to 1.00
0.65
None
Integral/Derivative
Time Unit
tidu
1, 0.1
1
,
0.1
1
Second
AT Calculated Gain
at-g
0.1to 10.0
Standard
Model: 0.8
Position-pro
portional
Model: 1.0
None
AT Hysteresis
at-h
Temperature input: 0.1 to 999.9
0.8
°
C or
°
F
Analog input: 0.01 to 9.99
0.20
%FS
Limit Cycle MV
Amplitude
lcma
5.0 to 50.0
20.0
%
Input Digital Filter
inf
0.0 to 999.9
0.0
Second
Moving Average Count
mav
OFF, 2, 4, 8, 16, or 32
OFF
*5
Times
MV Display
o-dp
OFF, ON
off
,
on
OFF
None
Automatic Display
Return Time
ret
OFF, 1 to 99
off
,
1
to
99
OFF
Second
Display Brightness
brgt
1 to 3
3
None
Alarm 1 Latch
a1lt
OFF, ON
off
,
on
OFF
None
Alarm 2 Latch
a2lt
OFF, ON
off
,
on
OFF
None
Alarm 3 Latch
a3lt
OFF, ON
off
,
on
OFF
None
Alarm 4 Latch
a4lt
OFF, ON
off
,
on
OFF
None
Move to Protect Level
Time
prlt
1 to 30
3
Second
Cold Junction
Compensation Method
cjc
OFF, ON
off
,
on
ON
None
Alarm 1 ON Delay
a1on
0 to 999 (0: ON delay disabled)
0
Second
Alarm 2 ON Delay
a2on
0 to 999 (0: ON delay disabled)
0
Second
Alarm 3 ON Delay
a3on
0 to 999 (0: ON delay disabled)
0
Second
Alarm 4 ON Delay
a4on
0 to 999 (0: ON delay disabled)
0
Second
Alarm 1 OFF Delay
a1of
0 to 999 (0: OFF delay disabled)
0
Second
Alarm 2 OFF Delay
a2of
0 to 999 (0: OFF delay disabled)
0
Second
Alarm 3 OFF Delay
a3of
0 to 999 (0: OFF delay disabled)
0
Second
Alarm 4 OFF Delay
a4of
0 to 999 (0: OFF delay disabled)
0
Second
MV at Stop and Error
Addition
mvse
OFF, ON
off
,
on
OFF
None
Auto/Manual Select
Addition
amad
OFF, ON
off
,
on
Standard
Model:OFF
Position-pro
portional
Model: ON
None
Manual Output Method
mant
HOLD or INIT
hold
,
init
HOLD
None
Manual MV Initial Value
mani
−
5.0 to 105.0 for standard control
*1
−
105.0 to 105.0 for heating/cooling control
*1
0.0
%
RT
rt
OFF, ON
off
,
on
OFF
None
HS Alarm Use
hsu
OFF, ON
off
,
on
ON
None
HS Alarm Latch
hsl
OFF, ON
off
,
on
OFF
None
HS Alarm Hysteresis
hsh
0.1 to 50.0
0.1
A
LBA Detection Time
lba
0 to 9999 (0: LBA function disabled)
0
Second
LBA Level
lbal
Temperature input: 0.1 to 999.9
8.0
°
C or
°
F
Analog input: 0.01 to 99.99
10.00
%FS
LBA Band
lbab
Temperature input: 0.0 to 999.9
3.0
°
C or
°
F
Analog input: 0.00 to 99.99
0.20
%FS
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
000
000
000
000
000
000
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...