![Omron E5C series User Manual Download Page 353](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592353.webp)
A - 27
A Appendices
E5@C Digital Temperature Controllers User’s Manual (H174)
A
-6 P
aram
eter Operation L
ists
A
A-6-6 Adv
anced F
unct
ion Setting Le
v
el
Auxiliary Output 1
Assignment
sub1
NONE: No assignment
none
ALM1
*Controllers
without HB
and HS
alarm
detection:
HA
None
O: Control output (heating)
o
C-O: Control output (cooling)
c-o
ALM1: Alarm 1
alm1
ALM2: Alarm 2
alm2
ALM3: Alarm 3
alm3
ALM4: Alarm 4
alm4
HA: Heater alarm (HB + HS)
ha
HB: Heater burnout alarm (HB)
hb
HS: Heater short alarm (HS)
hs
S.ERR: Input error
s.err
RS.ER: RSP input error
rs.er
P.END: Program end output
*3
p.end
RUN: RUN output
run
ALM: Integrated alarm
alm
WR1: Work bit 1
*4
wr1
WR2: Work bit 2
*4
wr2
WR3: Work bit 3
*4
wr3
WR4: Work bit 4
*4
wr4
WR5: Work bit 5
*4
wr5
WR6: Work bit 6
*4
wr6
WR7: Work bit 7
*4
wr7
WR8: Work bit 8
*4
wr8
Auxiliary Output 2
Assignment
sub2
Same as the Auxiliary Output 1 Assignment
parameter.
Same as the
Auxiliary
Output 1
Assignment
parameter.
ALM2
None
Auxiliary Output 3
Assignment
sub3
Same as the Auxiliary Output 1 Assignment
parameter.
Same as the
Auxiliary
Output 1
Assignment
parameter.
ALM3
None
Auxiliary Output 4
Assignment
sub4
Same as the Auxiliary Output 1 Assignment
parameter.
Same as the
Auxiliary
Output 1
Assignment
parameter.
ALM4
None
Integrated Alarm
Assignment
alma
0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
RSP input error: +128
49
None
Soak Time Unit
t-u
M: Minutes
H: Hours
m
,
h
M
None
Alarm SP Selection
alsp
SP-M: Ramp set point
SP: Set point
sp-m
,
sp
SP-M
None
Remote SP Input
rs-t
4-20: 4-20 mA
0-20: 0-20 mA
1-5V: 1-5 V
0-5V: 0-5 V
0-10: 0-10 V
4-20
,
0-20
,
1-5V
,
0-5V
,
0-10
4-20
None
Remote SP Enable
rspu
OFF, ON
off
,
on
OFF
None
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
000
000
000
000
000
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...