The following procedure sets the transfer output for an SP range of
−
50
to 200.
Operating Procedure
• Setting the Transfer Output Type
1
Press the
M
Key several times in the Initial Setting Level to
display
tr-t
(Transfer Output Type).
Initial Setting Level
2
Press the
U
or
D
Key to select
sp
.
The default is
off
.
• Setting the Transfer Output Upper Limit
1
Press the
M
Key several times in the Initial Setting Level to
display
tr-h
(Transfer Output Upper Limit).
Initial Setting Level
2
Press the
U
or
D
Key to set the value to 200.
The default is 1300.
• Setting the Transfer Output Lower Limit
1
Press the
M
Key several times in the Initial Setting Level to
display
tr-l
(Transfer Output Lower Limit).
Initial Setting Level
2
Press the
U
or
D
Key to set the value to
−
50.
The default is
−
200.
off
tr-t
Transfer Output
Type
sp
tr-t
1300
tr-h
Transfer Output
Upper Limit
200
tr-h
-200
tr-l
Transfer Output
Lower Limit
-50
tr-l
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...