6 Parameters
6 - 80
E5@C Digital Temperature Controllers User’s Manual (H174)
alma
Integrated Alarm Assignment
The integrated alarm must be assigned.
You can use the integrated alarm to output an OR of alarm 1, alarm 2, alarm 3, alarm 4, the
HB alarm, the HS alarm, the input alarm, and the RSP input alarm. Set this parameter to the
sum of the codes of the status for which to output an OR.
The default is 49 (i.e., an OR of alarm 1, the HB alarm, and the HS alarm is output). The
alarm 1 code is 1, the HB alarm code is 16, and the HS alarm code is 32: 1 + 16 + 32 = 49.
z
Related Parameters
Alarm Value 1 to 4 (Operation Level): Page 6-14
MV at Error (Adjustment Level): Page 6-33
HB ON/OFF (Advanced Function Setting Level): Page 6-63
HS Alarm Use (Advanced Function Setting Level): Page 6-74
Remote SP Enable (Advanced Function Setting Level): Page 6-81
t-u
Soak Time Unit
The Program Pattern parameter must not be set to
OFF.
• Set the soak time unit for the simple program function.
z
Related Parameters
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-46
Function
Setting
Code
Status
+1
Alarm 1
+2
Alarm 2
+4
Alarm 3
+8
Alarm 4
+16
HB alarm
+32
HS alarm
+64
Input error
+128
RSP input error
Setting range
Default
0 to 255
49
See
See
000
Function
Setting
Setting range
Default
m
: Minutes,
h
: Hours
m
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...