6 - 77
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Ad
v
a
n
ced
Fun
ctio
n Setting
Le
v
e
l
6
lbab
LBA Band
A Standard Model must be used.
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
• This parameter sets the LBA band.
• If a control deviation greater than the LBA band is not reduced when the LBA level is
exceeded, an loop burnout is detected.
z
Related Parameters
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-47
LBA Detection Time (Advanced Function Setting Level): Page 6-76
LBA Level (Advanced Function Setting Level): Page 6-76
Function
Setting
Setting range
Unit
Default
Temperature input
0.0 to 999.9
°
C or
°
F
3.0
Analog input
0.00 to 99.99
%FS
0.20
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...