![Omron E5C series User Manual Download Page 190](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592190.webp)
5 Advanced Operations
5 - 42
E5@C Digital Temperature Controllers User’s Manual (H174)
Simple programming is used.
The related parameters are as follows:
Program pattern: STOP
Soak time = 10 min
Wait band: 3
Operating Procedure
• Setting the Program Pattern
1
Press the
M
Key several times in the Initial Setting Level to
display
ptrm
(Program Pattern).
Initial Setting Level
2
Press the
U
or
D
Key to select
stop
(STOP).
The default is
off
.
• Setting the Soak Time
1
Press the
M
Key several times in the Adjustment Level to dis-
play
soak
(Soak Time).
Adjustment Level
2
Press the
U
or
D
Key to set the value to 10.
The default is 1 (min or h).
• Setting the Wait Band
1
Press the
M
Key several times in the Adjustment Level to dis-
play
wt-b
(Wait Band).
Adjustment Level
2
Press the
U
or
D
Key to set the value to 3.0.
The default is
off
.
STOP
PV
RSET
→
STRT
Set point
Wait band = 3
Soak time = 10 min
END display
END output
off
ptrn
Program Pattern
stop
ptrn
1
soak
Soak Time
10
soak
off
wt-b
Wait Band
3.0
wt-b
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...