A Appendices
A - 20
E5@C Digital Temperature Controllers User’s Manual (H174)
*1
This setting is not displayed for heating and cooling control or for floating position-proportional control.
Integral Time (Cooling)
c-i
Integral/Derivative Time Unit of 1 s: 0 to 9,999
Integral/Derivative Time Unit of 0.1 s: 0.0 to 999.9
233
233.0
Seconds
Derivative Time
(Cooling)
c-d
Integral/Derivative Time Unit of 1 s: 0 to 9,999
Integral/Derivative Time Unit of 0.1 s: 0.0 to 999.9
40
40.0
Seconds
Dead Band
c-db
Temperature input:
−
199.9 to 999.9
0.0
°
C or
°
F
Analog input:
−
19.99 to 99.99
0.00
%FS
Manual Reset Value
of-r
0.0 to 100.0
50.0
%
Hysteresis (Heating)
hys
Temperature input: 0.1 to 999.9
1.0
°
C or
°
F
Analog input: 0.01 to 99.99
0.10
%FS
Hysteresis (Cooling)
chys
Temperature input: 0.1 to 999.9
1.0
°
C or
°
F
Analog input: 0.01 to 99.99
0.10
%FS
Soak Time
soak
1 to 9999
1
min or h
Wait Band
wt-b
Temperature input: OFF or 0.1 to 999.9
off
,
0.1
to
999.9
OFF
°
C or
°
F
Analog input: OFF, 0.01 to 99.99
off
,
0.01
to
99.99
OFF
%FS
MV at Stop
mv-s
Standard:
−
5.0 to 105.0
Heating/cooling:
−
105.0 to 105.0
0.0
%
Floating position-proportional control or the Direct
Setting of Position-proportional MV parameter set to
OFF: CLOS, HOLD, or OPEN
clos
,
hold
,
open
HOLD
None
Close position-proportional control with the Direct
Setting of Position-proportional MV parameter set to
ON:
−
5.0 to 105.0
0.0
%
MV at PV Error
mv-e
Same as the MV at Stop parameter.
0.0
%
SP Ramp Set Value
sprt
OFF, 1 to 9,999
off
,
1
to
9999
OFF
EU/s,
EU/min,
EU/h
SP Ramp Fall Value
sprl
SAME, OFF, or 1 to 9,999
same
,
off
,
1
to
9999
SAME
EU/s,
EU/min,
EU/h
MV Upper Limit
ol-h
Standard control: MV lower limit + 0.1 to 105.0
Heating/cooling control: 0.0 to 105.0
100.0
%
Close position-proportional control: MV lower limit +
0.1 to 105.0
MV Lower Limit
ol-l
Standard control:
−
5.0 to MV upper limit
−
0.1
0.0
%
Heating/cooling control:
−
105.0 to 0.0
−
100.0
Close position-proportional control:
−
5.0 to MV
upper limit
−
0.1
0.0
MV Change Rate Limit
orl
0.0 to 100.0
(0.0: MV Change Rate Limit Disabled)
0.0
%/s
Position Proportional
Dead Band
db
Close position-proportional control: 0.1 to 10.0
4.0
%
Floating position-proportional control: 0.1 to 10.0
2.0
Open/Close Hysteresis
oc-h
0.1 to 20.0
0.8
%
Extraction of Square
Root Low-cut Point
sqrp
0.0 to 100.0
0.0
%
Work Bit * ON Delay
w1
to
8on
0 to 999
0
Seconds
Work Bit * OFF Delay
w1
to
8of
0 to 999
0
Seconds
Communications
Monitor
plcm
0 to 9999
ms
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
000
000
000
000
000
000
000
000
000
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...