6 Parameters
6 - 46
E5@C Digital Temperature Controllers User’s Manual (H174)
This parameter sets the type of control when using the simple program function.
ptrn
Program Pattern
• If the program pattern is set to
off
, the simple program will not operate.
• If the program pattern is set to
stop
, the RUN/STOP status will change to STOP after the
soak time has expired. If the program pattern is set to
cont
, control will continue in RUN
status after the soak time has expired.
z
Related Parameters
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
RUN/STOP (Operation Level) : Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Soak Time Unit (Advanced Function Setting Level): Page 6-80
cp
c-cp
Control Period (Heating)
Control Period (Cooling)
The cooling control output and heating control
output must be assigned to relay or voltage
outputs (for driving SSR).
The control must be set to 2-PID control.
For the Control Period (Cooling) parameter, the
control must be set to heating/cooling control.
• These parameters set the output periods. Set the control periods taking the control
characteristics and the electrical life of the relay into consideration.
• For standard control, use the Control Period (Heating) parameter. The Control Period
(Cooling) parameter cannot be used.
• When the heating control output is a current output, the Control Period (Heating)
parameter cannot be used.
• For heating/cooling control, the control period can be set independently for heating and
cooling. The Control Period (Heating) parameter is used for the heating control output,
and the Control Period (Cooling) parameter is used for the cooling control output.
z
Related Parameters
PID ON/OFF (Initial Setting Level): Page 6-44
000
Function
Setting
Setting range
Default
off
Simple program function turned OFF
off
stop
Go to STOP mode at end of program.
cont
Continue in RUN mode at end of program.
See
See
Function
Setting
Parameter name
Setting range
Unit
Default
Control Period
(Heating)
0.1, 0.2, 0.5, 1 to 99
Seconds
20 for relay output
2 for voltage output (for driving SSR)
Control Period
(Cooling)
0.1, 0.2, 0.5, 1 to 99
Seconds
20 for relay output
2 for voltage output (for driving SSR)
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...