6 Parameters
6 - 18
E5@C Digital Temperature Controllers User’s Manual (H174)
6-4
Adjustment Level
This level is for executing AT (auto-tuning) and other operations, and for set control parameters.
This level provides the basic Controller parameters for PID control (proportional band, integral time,
derivative time) and heating/cooling control.
To move to the Adjustment Level from the Operation Level,
press the
O
Key once.
• The set points 0 to 7 in the Adjustment Level are the set
values for switching the set point during multi-SP input.
• The following items are displayed for Controllers with CT
Inputs: Heater current monitors, Leakage current monitors,
HB alarm detection, and HS alarm detection.
• Adjustment level parameters can be changed after setting
the Operation/Adjustment Protect parameter to 0. Displays
and changing levels are not possible if the
Operation/Adjustment Protect parameter is set to 1 to 3.
Protection is set in the Protect Level.
Control in progress
Operation
Level
Adjustment
Level
Power ON
Press the
O
Key for less than 1 s.
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...