![background image](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592109.webp)
4 - 11
4 Basic Operation
E5@C Digital Temperature Controllers User’s Manual (H174)
4-3 Settin
g th
e Inp
u
t T
yp
e
4
4-3-1 Inp
ut T
y
pe
4-3
Setting the Input Type
The Controller supports four input types: resistance thermometer, thermocouple, infrared temperature
sensor, and analog inputs. Set the input type that matches the sensor that is used.
Additional Information
Changes that are made with key operations are applied when the
O
or
M
Key is pressed. They
are also applied if you do nothing for 3 seconds or longer.
4-3-1
Input Type
The following example shows how to set a K thermocouple for
−
20.0 to
500.0
°
C (input type 6).
Operating Procedure
1
Press the
O
Key for at least 3 seconds to move from the
Operation Level to the Initial Setting Level. The
in-t
(Input
Type) parameter will be displayed.
Initial Setting Level
2
Press the
U
or
D
Key to select
6
(K thermocouple at
−
20.0 to
500.0
°
C).
The default is
5
(5: K thermocouple at
−
200 to 1,300
°
C).
5
in-t
Input Type
6
in-t
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...