![Omron E5C series User Manual Download Page 95](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592095.webp)
3 - 17
3 Part Names and Basic Procedures
E5@C Digital Temperature Controllers User’s Manual (H174)
3-4 Pr
oced
ures after T
u
rning
ON th
e P
o
wer
S
u
pp
ly
3
3-4-2 Basic Procedu
re
8
Absolute-value
upper-limit
alarm
The alarm output is ON while the
PV is equal to or higher than the
alarm value.
9
Absolute-value
lower-limit
alarm
The alarm output is ON while the
PV is equal to or lower than the
alarm value.
10
Absolute-value
upper-limit
alarm with
standby
sequence
This alarm provides a standby
sequence.
The alarm output is ON while the
PV is equal to or higher than the
alarm value.
11
Absolute-value
lower-limit
alarm with
standby
sequence
This alarm provides a standby
sequence.
The alarm output is ON while the
PV is equal to or lower than the
alarm value.
12
Loop Burnout
Alarm (LBA)
(Valid only for
alarm 1 on a
Standard
Model.)
The alarm output turns ON when
the control loop is broken.
There is assumed to be a loop burnout alarm if
the control deviation (SP
−
PV) is greater than
the threshold set in the LBA Level parameter
and if the PV is not reduced by at least the
value set in the LBA Band parameter within a
specific period of time. The LBA detection time
and LBA band are set in parameters.
Set
value
Alarm type
Description
Operation
ON
OFF
0
Temperature
Upper-limit alarm
point (e.g., 100
°
C)
Alarm value (e.g., 100
°
C)
Example:
ON
OFF
0
Temperature
Lower-limit alarm
point (e.g., 100
°
C)
Example:
Alarm value (e.g., 100
°
C)
ON
OFF
0
Temperature
Upper-limit alarm
point (e.g., 100
°
C)
Alarm value (e.g., 100
°
C)
Example:
ON
OFF
0
Temperature
Lower-limit alarm
point (e.g., 100
°
C)
Example:
Alarm value (e.g., 100
°
C)
ON
SP
MV
LBA Alarm Output
PV
100%
0%
OFF
Time
Time
Time
LBA detection time
LBA band
LBA level
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...