5 Advanced Operations
5 - 16
E5@C Digital Temperature Controllers User’s Manual (H174)
Set the set point upper and lower limits in the Set Point Upper Limit and Set Point Lower Limit parame-
ters in the Initial Setting Level. In this example, it is assumed that the input type is set to a K thermocou-
ple with a temperature range of
−
200 to 1300
°
C.
5-5-2
Setting
Set the upper and lower limits for the set point.
Set Point Upper Limit = 1000
Set Point Lower Limit =
−
100
Operating Procedure
• Setting the Set Point Upper Limit
1
Press the
M
Key several times in the Initial Setting Level to
display
sl-h
(Set Point Upper Limit).
Initial Setting Level
2
Press the
U
or
D
Key to set the value to 1000.
The default is 1300.
• Setting the Set Point Lower Limit
1
Press the
M
Key several times in the Initial Setting Level to
display
sl-l
(Set Point Lower Limit).
Initial Setting Level
2
Press the
U
or
D
Key to set the value to
−
100.
The default is
−
200.
−
200
−
100
1300
1000
Input setting range
Set point limiter
1300
sl-h
Set Point
Upper-limit
1000
sl-h
-200
sl-l
Set Point
Lower Limit
-100
sl-l
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...