![Omron E5C series User Manual Download Page 175](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592175.webp)
5 - 27
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-10 Alarm
Dela
y
s
5
5-10-1 Alar
m Dela
ys
Use the following procedure to set ON and OFF delays for the alarm 1.
An ON delay of 5 seconds and an OFF delay of 10 s will be set.
Operating Procedure
• Setting the Alarm 1 ON Delay
1
Press the
M
Key several times in the Advanced Function Set-
ting Level to display
a1on
(Alarm 1 ON Delay).
Advanced Function Setting
Level
2
Press the
U
or
D
Key to set the value to 5.
The default is 0.
• Setting the Alarm 1 OFF Delay
1
Press the
M
Key several times in the Advanced Function Set-
ting Level to display
a1of
(Alarm 1 OFF Delay).
Advanced Function Setting
Level
2
Press the
U
or
D
Key to set the value to 10.
The default is 0.
0
a1on
Alarm 1 ON
Delay
5
a1on
0
a1of
Alarm 1 OFF
Delay
10
a1of
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...