6 - 13
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-3 Op
er
a
tion
Le
v
el
6
This parameter starts and stops the control operation.
sktr
Soak Time Remain
The Program Pattern parameter must not be set to
OFF.
• This parameter measures and displays the remaining time of the soak time for the simple
program function.
z
Related Parameters
Program Start (Operation Level): Page 6-12
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-46
Soak Time Unit (Advanced Function Setting Level): Page 6-80
r-s
RUN/STOP
The Event Input Assignment 1 to 6 parameters
must not be set to RUN/STOP.
When
run
(RUN) is selected, control is started. When
stop
(STOP) is selected, control is
stopped. The STOP indicator will light when control is stopped.
The default is
run
.
This parameter will not be displayed if an event input is set to “RUN/STOP.”
000
Function
Monitor
Monitor range
Unit
0 to 9999
min or h
See
See
Operation
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...