5-18 Setting
th
e PF K
e
y
5
5-18-1 PF
Setting
(Fu
nction K
e
y)
5-18 Setting the PF Key
*1
When AT cancel is specified, it means that AT is cancelled regardless of whether the AT currently being
executed is 100% AT or 40% AT.
*2
Alarms 1 to 4, the HB alarm, and the HS alarm are cancelled.
*3
For details on auto/manual operations using the PF Key, refer to 5-12 Performing Manual Control.
*4
AT-1 can be set for heating/cooling control or for floating position-proportional control, but the setting will be
disabled.
Note1: Pressing the PF Key for at least one second executes operation according to the set value.
(However, if Digit Shift is set, operation will be in less than one second.) When the Monitor/Setting
Item parameter is selected, however, the display is changed in order from Monitor/Setting Item 1 to 5
each time the key is pressed.
2: This function is enabled when PF Key Protect is OFF.
5-18-1 PF Setting (Function Key)
PF Setting (Advanced
Function Setting Level)
• Pressing the PF Key for at least one second executes the operation set in the
PF Setting parameter. The default is
shft
(digit shift).
Set value
Display
Setting
Function
OFF
off
Disabled
Does not operate as a function key.
RUN
run
RUN
Specifies RUN status.
STOP
stop
STOP
Specifies STOP status.
R-S
r-s
RUN/STOP reverse
operation
Specifies reversing the RUN/STOP operation status.
AT-2
at-2
100% AT
Execute/Cancel
Specifies reversing the 100% AT Execute/Cancel status.*1
AT-1
at-1
40% AT
Execute/Cancel
Specifies reversing the 40% AT Execute/Cancel status.*1 *4
LAT
lat
Alarm Latch Cancel
Specifies canceling all alarm latches.*2
A-M
a-m
Auto/Manual
Specifies reversing the Auto/Manual status.*3
PFDP
pfdp
Monitor/Setting Item
Specifies the monitor/setting item display. Select the monitor
setting item according to the Monitor/Setting Item 1 to 5
parameters (Advanced Function Setting Level).
SHFT
shft
Digit Shift
Operates as a Digit Shift Key when settings are being
changed.
shft
pf
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...