7 User Calibration
7 - 12
E5@C Digital Temperature Controllers User’s Manual (H174)
Use the following procedure to calibrate the transfer output for 1 to 5 V.
1. Connect a DMM to the transfer output terminals.
2. Press the
M
Key to display the parameter for the transfer output.
3. The calibration display for 5 V will be displayed. Press the
U
or
D
Key until the
DMM monitor value changes to 5 V.
Press the
M
Key. The calibration settings will be temporarily registered.
4. The calibration display for 1 V will be displayed. Press the
U
or
D
Key until the
DMM monitor value changes to 1 V.
Press the
M
Key. The calibration settings will be temporarily registered.
5. To cancel saving the temporarily registered calibration data to non-volatile
memory, press the
M
Key without pressing the
U
Key, i.e., while
no
is displayed
in the No. 2 display.
Press the
U
Key. The No. 2 display changes to
yes
. Release the key and wait 2
seconds or press the
M
Key. This saves the temporarily registered calibration data
in non-volatile memory.
6. The Calibration Mode is ended by turning OFF the power supply.
Input power supply
DMM
E5CC
+
−
Input power supply
DMM
E5EC/E5AC
+
−
11
12
16
18
1
2
31
33
str
no
v 5.t
5680
V 1.t
0001
str.t
no
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...