![Omron E5C series User Manual Download Page 197](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592197.webp)
5 - 49
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-17 Setting
the
Wid
th
of M
V
V
ariation
5
5-17-1 MV C
hange Rate
Limit
5-17 Setting the Width of MV Variation
5-17-1 MV Change Rate Limit
MV Change Rate
Limit
• The MV change rate limit sets the maximum allowable width of change per
second in the MV (or the change per second in the valve opening for a
Position-proportional Model). If the change in the MV exceeds this setting, the
MV will be changed by the MV change rate limit until the calculated value is
reached. This function is disabled when the setting is 0.0.
• The MV change rate limit does not function in the following situations:
• In Manual Mode
• During ST execution (Cannot be set when ST is ON.)
• During AT execution
• During ON/OFF control
• While stopped (during MV at Stop output)
• During MV at PV Error output
Parameter name
Setting rage
Unit
Default
Level
MV Change Rate Limit
0.0 to 100.0
%/s
0.0
Adjustment Level
000
0.0
orl
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...