6 Parameters
6 - 8
E5@C Digital Temperature Controllers User’s Manual (H174)
Process Value/Set Point 1
PV/SP No. 1 Display Selection must not be set to 0.
Process Value/Set Point 2
PV/SP No. 2 Display Selection must not be set to 0.
The following table shows the contents of the No. 1, 2, and 3 displays, according to the set-
ting of the PV/SP Display Screen Selection parameter.
*1
The set value of the Alarm Value 1 parameter is displayed even if it is not valid due to the setting
of the Alarm 1 Type parameter.
For a temperature input, the decimal point position depends on the currently selected sen-
sor, and for an analog input it depends on the Decimal Point parameter setting.
PV/SP Display Selections
z
Related Parameters
PV/SP Display Selection (Advanced Function Setting Level): Page 6-88
Function
Setting
Set value
No. 1 display
No. 2 display
No. 3 display (E5EC/E5AC only)
0
Nothing is displayed.
Nothing is displayed.
Nothing is displayed.
1
Process value
Set point
Nothing is displayed.
2
Process value
Nothing is displayed.
Nothing is displayed.
3
Set point
SP (character display)
Nothing is displayed.
4
Process value
Set point
MV (valve opening for
Position-proportional Models)
5
Process value
Set point
Multi-SP No.
6
Process value
Set point
Soak time remain
7
Process value
Set point
Internal set point (ramp SP)
8
Process value
Set point
Alarm value 1
*1
000
Monitor range
Unit
Process value
Temperature input: The specified range for the specified sensor.
Analog input: Scaling lower limit
−
5% FS to Scaling upper limit +5%
FS
EU
Setting range
Unit
Set point
SP lower limit to SP upper limit
EU
*
The default is 1 for models other than the E5
@
C-
@
-0
@
.
Parameter
Default
PV/SP No. 1 Display Selection
4*
PV/SP No. 2 Display Selection
0
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...