6 - 79
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Ad
v
a
n
ced
Fun
ctio
n Setting
Le
v
e
l
6
sub1
Auxiliary Output 1 Assignment
There must be an auxiliary output 1.
sub2
Auxiliary Output 2 Assignment
There must be an auxiliary output 2.
sub3
Auxiliary Output 3 Assignment
There must be an auxiliary output 3.
sub4
Auxiliary Output 4 Assignment
There must be an auxiliary output 4.
• These parameters set the function to assign to auxiliary outputs 1 to 4.
*1
If
c-o
is assigned for standard control, a value equivalent to 0% will be output.
*2
If heating/cooling control is used with an E5CC, E5CC-U, E5DC Controller that does not have
control output 2,
c-o
is automatically assigned to auxiliary output 2. If heating/cooling control is
used with an E5EC or E5AC Controller that does not have control output 2,
c-o
is automatically
assigned to auxiliary output 4 if there are four auxiliary outputs and to auxiliary output 2 if there
are only two auxiliary outputs. (If the Controller has only one auxiliary output, an output is not
automatically allocated for the control output for cooling).
*3
Can be selected when the Program Pattern parameter is set to OFF, but the function will be
disabled.
*4
WR1 to WR8 are not displayed when the logic operation function is not used.
*5
If the Controller is equipped with HB/HS alarm detection, it is set by default to
ha
(Heater Alarm).
000
Setting range
Default
none
:
Disabled
Auxiliary Output 1 Assignment:
alm1
*5
Auxiliary Output 2 Assignment:
alm2
*2
Auxiliary Output 3 Assignment:
alm3
*2
Auxiliary Output 4 Assignment:
alm4
*2
o
:
Control output (heating)
c-o
:
Control output (cooling)
*1
alm1
:
Alarm 1
alm2
:
Alarm 2
alm3
:
Alarm 3
alm4
:
Alarm 4
ha
:
Heater alarm
hb
:
HB alarm
hs
:
HS alarm
s.err
:
Input error
rs.er
:
RSP input error
p.end
:
Program end output
*3
run
:
RUN output
alm
:
Integrated Alarm
wr1
:
Work bit 1
*4
wr2
:
Work bit 2
*4
wr3
:
Work bit 3
*4
wr4
:
Work bit 4
*4
wr5
:
Work bit 5
*4
wr6
:
Work bit 6
*4
wr7
:
Work bit 7
*4
wr8
:
Work bit 8
*4
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...