A Appendices
A - 22
E5@C Digital Temperature Controllers User’s Manual (H174)
Alarm 1Type
alt1
0:
Alarm function OFF
1:
Upper and lower-limit alarm
2:
Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit range alarm
5: Upper- and lower-limit alarm with standby
sequence
6: Upper-limit alarm with standby sequence
7: Lower-limit alarm with standby sequence
8: Absolute-value upper-limit alarm
9: Absolute-value lower-limit alarm
10: Absolute-value upper-limit alarm with standby
sequence
11: Absolute-value lower-limit alarm with standby
sequence
12: LBA (Loop Burnout Alarm) (A Standard Model
must be used.)
13: PV change rate alarm
14: SP absolute-value upper-limit alarm
15: SP absolute-value lower-limit alarm
16: MV absolute-value upper-limit alarm
17: MV absolute-value lower-limit alarm
18: RSP absolute-value upper-limit alarm (There
must be a remote SP input.)
19: RSP absolute-value lower-limit alarm (There
must be a remote SP input.)
2
None
Alarm 1 Hysteresis
alh1
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
0.2
°
C or
°
F
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.02
%FS
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
0.50
%
Alarm 2 Type
alt2
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
2
None
Alarm 2 Hysteresis
alh2
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
0.2
°
C or
°
F
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.02
%FS
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
0.50
%
Alarm 3 Type
alt3
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
2
None
Alarm 3 Hysteresis
alh3
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
0.2
°
C or
°
F
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.02
%FS
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
0.50
%
Alarm 4 Type
alt4
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
2
None
Alarm 4 Hysteresis
alh4
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
0.2
°
C or
°
F
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.02
%FS
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
0.50
%
Control Output 1 Signal
o1st
4-20: 4-20 mA
0-20: 0-20 mA
4-20
,
0-20
4-20
None
Parameters
Characters
Setting (monitor) value
Display
Default
Unit
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...