5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-4 Using
Event Inp
u
ts
5
5-4-3 Oper
ation Comma
nds Other than Multi-SP
The MANU indicator will light during manual control.
z
Controlling the Start of the Simple Program Function
When the Event Input Assignment parameter is set to PRST (program start), the program will start
when the event input turns ON. The program will be reset when the input turns OFF and the
RUN/STOP status will automatically switch to STOP mode. If the program END output is ON, the
program END output will turn OFF.
z
Control by Inverting Direct/Reverse Operation
When the Event Input Assignment parameter is set to DRS (Invert Direct/Reverse Operation) and
the Direct/Reverse Operation parameter is set for reverse operation, control starts with direct
operation (cooling control) when the event input turns ON and control starts with reverse operation
(heating control) when the event input turns OFF.
z
Switching the SP Mode
When the Event Input Assignment parameter is set to RSP (SP mode switch), operation with a
remote SP will start when the event input turns ON. Operation with a local SP will start when the
event input turns OFF. The RSP operation indicator will light during Remote SP Mode.
z
Switching 100% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-2 (100% AT Execute/Cancel), 100% AT will
be executed when the event input turns ON and will be cancelled when the input turns OFF.
z
Switching 40% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-1 (40% AT Execute/Cancel), 40% AT will
be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Input contact
Status
Event input
OFF
Automatic
Event input
ON
Manual
Setting
Input contact
Status
Event input
OFF
Reset
Event input
ON
Start
Setting
Input contact
Direct/Reverse
Operation parameter
Status
Event input
OFF
Direct operation (cooling)
Direct operation (cooling)
Reverse operation
(heating)
Reverse operation
(heating)
Event input
ON
Direct operation (cooling)
Reverse operation
(heating)
Reverse operation
(heating)
Direct operation (cooling)
Setting
Input contact
Status
Event input
OFF
Local SP
Event input
ON
Remote SP
Setting
Input contact
Status
Event input
OFF
100% AT cancelled
Event input
ON
100% AT executed
Setting
Input contact
Status
Event input
OFF
40% AT cancelled
000
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...