4 Basic Operation
4 - 8
E5@C Digital Temperature Controllers User’s Manual (H174)
4-2
Initial Setting Examples
Initial hardware setup, including the sensor input type, alarm types, control periods, and other settings,
is done using parameter displays. The
O
and
M
Keys are used to switch between parameters, and the
amount of time that you press the keys determines which parameter you move to.
This section describes three typical examples.
*
If the Controller is equipped with HB/HS alarm detection, the Alarm 1 Type is not displayed for the default
settings. To use alarm 1, set an output assignment to alarm 1. For details, refer to 4-6-3 Assigned Output
Functions (Assigning Control Outputs Is Not Supported for Position-proportional Models.).
Explanation of Examples
Example 1
0
in-t
onof
intl
100
in-h
0
in-l
onof
intl
0
25
M
M
M
Changing Parameters
A image means that there are parameters.
Continue pressing the
M
Key to change parameters
until you reach the intended parameter.
Changing Numbers
Numeric data and selections in each
screen can be changed by using the
U
and
D
Keys.
0
25
M
M
M
M
M
M
Initial Setting Level
Operation Level
5
in-t
onof
cntl
2
alt1
100
25
run
r-5
20
al-1
100
20
onof
pid
run
stop
Input type:
5 (K thermocouple,
−
200
°
C to 1,300
°
C)
Control method: ON/OFF control
Alarm type:
2 (upper limit)
Alarm value 1:
20
°
C (deviation)
Set point:
100
°
C
Setup Procedure
Power ON
Set input
specifications
Set control
specifications
Set alarm type
Set SP and alarm values
Start operation
Power ON
Operation Level
PV/SP
Press the
O
Key for at least 3 s.
Control stops.
Initial Setting Level
Input Type:
5
Check that
control method is
ON/OFF control.
ON/OFF
control:
PID control:
Check alarm type.
Check input type.
Alarm 1 Type*:
2
Press the
O
Key for at least 1 s.
Control starts.
Operation Level
Use the
U
and
D
Keys to set the
SP to 100
°
C.
PV/SP:
Confirm that
control is running.
Running
Stopped:
Use the
U
and
D
Keys to set the
alarm value to
20
°
C.
Alarm Value 1:
Start operation.
An
s.err
error will be
displayed if the power
supply is turned ON before
the sensor is connected.
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...