6 Parameters
6 - 36
E5@C Digital Temperature Controllers User’s Manual (H174)
oc-h
Open/Close Hysteresis
A Position-proportional Model must be used.
• The Open/Close Hysteresis parameter is used to shift the ON and OFF points for the
open output and close output to prevent output chattering.
z
Related Parameters
Position Proportional Dead Band (Adjustment Level): Page 6-35
sqrp
Extraction of Square Root Low-cut
Point
The input type must be an analog input, and the
Extraction of Square Root Enable parameter must
be set to ON.
• This parameter sets the extraction of square root low-cut point used for the inputs. The
data after extracting the square root is shown below.
• The low-cut point is used for extracting the square root for flowrate sensors.
z
Related Parameters
Extraction of Square Root Enable (Initial Setting Level): Page 6-58
Function
Setting
Setting range
Unit
Default
0.1 to 20.0
%
0.8
See
See
000
Function
0
Argument 1 (input data)
Operation result
100% FS
100% FS
Extraction of square
root low-cut point
Setting
Setting range
Unit
Default
0.0 to 100.0
%
0.0
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...