![background image](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592117.webp)
4 - 19
4 Basic Operation
E5@C Digital Temperature Controllers User’s Manual (H174)
4-6 Setting Ou
tpu
t Sp
ecification
s
4
4-6-4 A
u
xiliar
y Output O
penin
g or Closing
in Alar
m
• When "close in alarm" is set, the status of the auxiliary output is output unchanged. When "open in
alarm" is set, the status of the auxiliary output function is reversed before being output.
• Each auxiliary output can be set independently.
• These settings are made in the Auxiliary Output 1 to 4 Open in Alarm parameters (Advanced
Function Setting Level).
• The default is
n-o
: Close in Alarm.
• The alarm output will turn OFF (i.e., the relay contacts will open) when power is interrupted and for
about two seconds after the power is turned ON regardless of the setting of the Auxiliary Output 1 to
4 Open in Alarm parameter.
• Setting Auxiliary Output 2
1
Press the
M
Key several times in the Advanced Function
Setting Level to display
sub2
(Auxiliary Output 2 Assignment).
Advanced Function Setting
Level
2
Press the
U
or
D
Key to set the parameter to
alm2
.
The default is
alm2
(Alarm 2).
4-6-4
Auxiliary Output Opening or Closing in Alarm
Auxiliary output
functions 1 to 4
Auxiliary output
Indicators
(SUB1 to SUB4)
Close in Alarm
(
n-o
)
ON
ON
Lit
OFF
OFF
Not lit
Open in Alarm
(
n-c
)
ON
OFF
Lit
OFF
ON
Not lit
alm2
sub2
Auxiliary Output
2 Assignment
alm2
sub2
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...