background image

 

US 

  +1 650 543 8166

 

[email protected]

 

 

Other markets

 

 

  +45 4567 0300

 

[email protected]

 

www.windowmaster.com 

 

WCC 3xx install 1711-Firmware v123 UL - UK    ©WindowMaster 2016, 2017   ®WindowMaster is a registred trademark used under the license by WindowMaster International A/S 
WindowMasterInternational A/S, Skelstedet 13, DK-2950 Vedbæk 

 

 

 
 

WCC 310 & WCC 320 UL 

Plus versions 

 

Installation instruction 

 

UL MotorController 

 

 

(Version 1711 

– for firmware from version 1.23 (main card) &  

from version 1.06  (motor line card)) 

 

 

 

 

Save this installation instruction to the end user

 

 
 
 

 

 

Summary of Contents for MotorController WCC 310 UL

Page 1: ...2017 WindowMaster is a registred trademark used under the license by WindowMaster International A S WindowMasterInternational A S Skelstedet 13 DK 2950 Vedbæk WCC 310 WCC 320 UL Plus versions Installation instruction UL MotorController Version 1711 for firmware from version 1 23 main card from version 1 06 motor line card Save this installation instruction to the end user ...

Page 2: ...d actuators 10 8 1 3 Max cable length actuators with MotorLink 11 9 Cable plan for connection to WCC 310 320 Plus version 12 10 Description of cards and mains connection 13 WCC connection to mains and power supply units WCA 3P3 WCA 3P4 and WCA 3P6 13 Connections between cards 13 Main control card WCA 3CP Plus Version 14 Motor line card WCA 3M4 WCA 3M8 21 Keypad card WCA 3KI 22 Power supply card WC...

Page 3: ...et configuration 36 13 Status main menu 36 14 Manual operation and main menu 37 15 Configuration missing main menu 37 16 Hardware error main menu 37 17 View all details main menu 37 18 Remote control of MotorController 38 19 Commissioning and test run 38 The MotorController is completely installed without the operating voltage applied 38 With mains voltage 39 Ventilation keypad 39 Wind rain detect...

Page 4: ...ge to assets The connection of the MotorController is reserved for qualified personnel Disconnect all poles of the MotorController from the supply voltage prior to opening installation or assembling Installation and use according to the national regulations Application The MotorController is exclusively designed for the automatic opening and closing of windows flaps or doors Always check that your...

Page 5: ...ards WCA 3FK fieldbus card fieldbus interface for KNX WCA 3FM fieldbus card fieldbus interface for BACnet MSTP WCA 3FB fieldbus card fieldbus interface for BACnet IP Installation of cards may only be done when there is no power on the MotorController Motor line and input cards are ordered together with the MotorController and mounted to the MotorController from the factory side whereas the fieldbu...

Page 6: ...WCA 3KI WCC 320 P 0612 U1 Plus version 10 motor lines 12 keypads inputs 1 x WCA 3CP 1 x WCA 3M8 1 x WCA 3KI WCC 320 P 1012 U1 Max numbers of actuators per motor line and MotorController The table shows the maximum number of actuators which can be connected per motor line and MotorController depending on the type of the actuator MotorController and connected card The total power consumption of all ...

Page 7: ...bus interface for BACnet MSTP incl cover sold separately not factory mounted WCA 3FM Fieldbus card with field bus interface for BACnet IP incl cover sold separately not factory mounted WCA 3FB Rain sensor WLA 331 Rain wind speed sensor WLA 330 Rain wind speed sensor with pulse output WLA 340 Wind speed sensor Wind direction sensor WOW 201 WOW 202 Bracket for junction box WOW 203 Junction box for W...

Page 8: ...y closed circuit Actuators with MotorLink are monitored by data communication LED message OK and fault Green Yellow CPU working fault Connection cable Actuators Other components Mains flexible max 6 mm solide max 10 mm Min 22AWG 300V 80 C Listed Recognized to UL 13 min 0 2mm max 1 5mm Listed Recognized to UL 13 Mains must be done per relevant Electrical Code For permanent connection rigid or flexi...

Page 9: ... Ensure that the ventilation buttons are visible and well accessible Do not install behind protruding walls door MotorControllers or hidden by the building structure Assembly instructions Always have assembly installation repair and maintenance of ventilation systems carried out by qualified personnel trained for this purpose Rules to be adhered to for setting up and installation The following saf...

Page 10: ...p in the line 2 Volt Actuating current Sum of all actuator power consumption per motor line Note do not use the PE wire green yellow wire in the actuator cable Example Max actuator cable length with cable cross section 0 75mm2 and actuator current 2A 2 x 56 x 0 75 2 x 2 21m 8 1 2 Max cable length 24V standard actuators The actuator supply cable must have 2 wires If monitoring is desired use min 3 ...

Page 11: ...regardless of the result of the above mentioned formula Actuators with MotorLink Do not use the PE wire green yellow wire cable cross section a Total actuator current I 3 wire 0 75mm 3 wire 1 50 mm 5 wire 1 50 mm 2 wire parallel 3 wire 2 50 mm 5 wire 2 50 mm 2 wire parallel 3 wire 4 00 mm 1A 42m 50m 2A 21m 40m 50m 3A 14m 28m 50m 47m 50m 4A 11m 21m 42m 35m 5A 8m 17m 34m 28m 50m 45m 6A 7m 14m 28m 23...

Page 12: ...12 9 Cable plan for connection to WCC 310 320 Plus version The above plan shows a WCC 320 MotorController ...

Page 13: ...roller chapter 3 2 WCC connection to mains and power supply units WCA 3P3 WCA 3P4 and WCA 3P6 The MotorController WCC 310 is supplied with a 305W SMPS power supply WCA 3P3 The MotorController WCC 320 is supplied with a 605W SMPS power supply WCA 3P4 The power supply is regardless of size placed in the bottom of the MotorController beneath the motor line and input card An AUX WCA 3P6 to which mains...

Page 14: ...host and USB device Connection for fieldbus card Touch screen for configuration commissioning and maintenance S1 X1 X2 The WCA 3CP card has 2 motor lines X1 and X2 for connection of 24V standard or MotorLink actuators 24V standard actuators 1 1 24V 0V 1 2 1 3 0V 24V 2 1 24V 0V 2 2 1 3 0V 24V MotorLink actuator 1 1 0V 1 2 Communication 1 3 24V 2 1 0V 2 2 Communication 2 3 24V The number of actuator...

Page 15: ...ples with 20A power consumption a 8 pcs WMX 826 1 b 4 sets of 2 pcs WMX 826 2 c 4 pcs WMU 861 1 d 2 sets of 2 pcs WMU 842 2 Connection variant of standard actuators on motor line X1 MotorLink actuators Examples with actuators per motor line Ex 1 4 pcs WMX 823 1 Ex 2 2 pcs WMU 842 2 Ex 3 3 pcs WMU 826 3 Allowed actuator combinations on a MotorLink motor line The two motor lines on the CP card can e...

Page 16: ...connection via WSK Link X5 and X6 are used on the master panel whereas X11 is used on the slave panel For connection of WSK Link see X11 Data 5 1 24V 5 2 Communication 5 3 0V 6 1 24V 6 2 Communication 6 3 0V S1 X9 Solid state outputs one solid state output for transmission of fault signal and 2 free configurable Data 9 1 Fault Open contact Fault closed contact OK 9 2 Fault Open contact Fault close...

Page 17: ...30 or WLA 340 rain sensor WLA 331 Or connection of intelligent weather station wind direction dependent ventilation e g wind speed sensor WOW 201 wind direction sensor WOW 202 junction box and brackets WOW 203 304 and rain sensor WLA 331 Data 10 1 24V AUX 10 2 Wind speed 10 3 GND 0V 10 4 24V not active in power saving 10 5 Rain 10 6 GND 0V With the default values are input Active if the contact re...

Page 18: ...lle s touch screen Data 10 1 24V AUX 10 2 Wind speed 10 3 GND 0V 10 4 24V 10 5 Rain 10 6 GND 0V Example 2 Wind direction dependent ventilation intelligent weather station Data 10 1 24V AUX 10 2 Wind speed Direction 10 3 GND 0V 10 4 24V 10 5 Rain 10 6 GND 0V As the weather station is monitored by both communication and time out wind without time any cable errors will be registered ...

Page 19: ...via X11 It is possible to connect several MotorControllers in a master slave connection However the max total number of MotorControllers on the WSK Link must not exceed 10 units The max cable length between two units must not exceed 200m see examples below for how to connect the MotorControllers Sharing of signals from weather station Example 1 Example 2 MotorController 2 and 3 are both master and...

Page 20: ...nnection for power supply J2 Power to motor line card WCA 3M4 WCA 3M8 J3 Connection to AUX WCA 3P6 120V supply J4 Connection for motor line card WCA 3M4 WCA 3M8 J7 2 x Ethernet connection J8 USB host Used to store configurations and to start an event log for e g trouble shooting J9 USB device Used for remote control and to flash the MotorController J10 Connection for fieldbus card P1 Power supply ...

Page 21: ... J4 on the WCA 3CP S2 X1 X8 For connection of 24 Standard actuators or MotorLink actuators Data x 1 24V 0V x 2 ML Communication x 3 0V 24V For actuator connections please see explanation in section WCA 3CP main control card under X1 X2 and Max number of actuators per card F1 F8 3 15A fuse for motorline WCA 308 J3 Connection to main control card WCA 3CP J4 Power connection from control card WCA 3CP...

Page 22: ...uator card The WCA 3KI is connected to WCA 3M4 WCA 3M8 via cable J1 on the WCA 3KI and J6 on the WCA 3M4 WCA 3M8 S3 X1 X10 Data x 1 Open x 1 x 2 Close x 2 x 3 GND 0V For input connections please see explanation in section WCA 3CP main control card under X3 X4 J1 Connection to motor line card WCA 3M4 and WCA 3M8 ...

Page 23: ...card with BACnet IP interface The connection of a fieldbus card enables communication and access to the available bus objects depending on the chosen system There is a set of KNX and BACnet objects available for each motor line and motor group which provides the options for status and commands Status options E g actual position fault and operation status and the max opening angle degrees Command o...

Page 24: ...4 Showing the sub menu Help text Help text The touch screen has a help function with text explaining the menu item The help text occurs when the menu item is pressed text on white background For displaying the help text press the item e g Motor type the help text appears to turn off the help text press the screen Icons The MotorController has icons for quick viewing of fire conditions hardware OK ...

Page 25: ...ewing angle see chapter 12 12 System It is also possible to change the log out time which is the time that the access to the access level is open the touch screen in on see chapter 12 10 Log in To configure a sub menu press the light blue number field enter value the number of the motor line change factory settings etc The setting which can be entered depends of the type of the sub menu accept on ...

Page 26: ... with actuators connected are to be configured in motor group Motor lines with no actuator connected are set to none Since 24V actuators and actuators with MotorLink are not to be configured exactly the same way both type of actuators are listed below with the settings that are to be configured for each actuator type Be aware that both types of actuators can be connected to the MotorController at ...

Page 27: ...point zero of the actuator has been determined Light grey number The motor line are configured with No actuator are connected Blue Configuration is missing Motor group Motorlines can be assigned to motor groups See the example Example of motor lines motor groups in the beginning of this chapter for further details 12 3 1 Motor group configuration Press Motor group and the overview of the motor gro...

Page 28: ...e inputs are to be configured Which item to be configured depends on the type of input see description below Local input configuration Overview Local input Example of overview Local input with connected input card WCA 3KI S1 Close and S1 Open are the two buttons on the board Configuration of local input X3 and X4 Input X3 and X4 on WCA 3CP and X1 X10 on WCA 8KI binary If local inputs are connected...

Page 29: ...e allowed to open e g 10 to open despite it rains Input shall be configured in Configuration of local input 1 In the motor groups configure the input with the function Safety 2 Configure the motor groups when anything else than close 0 is desired Note motor groups also receive Safety signals from the smoke zones they are associated with see below for further information Local output On the WCA 3CP...

Page 30: ...Logic function c Status when active d Time out The appendix contains all the items that can be configured see appendix for detailed explanation Weather station type Here is to be selected which type of weather station none WOW or WLA that is connected The menu Weather is only used for input from WCA 3CP input S1X10 2 for wind speed from WLA 340 Input S1X10 2 is also used in combination with weathe...

Page 31: ...st depend on an external event or situation stage To be used where window flabs are overlapping or where the windows cannot open more than 15 if the blinds are down a s o The sequence control can be controlled depending on the position of a different motor line the state of a local input the state of a KNX object the state of a BACnet object Sequence control configuration Activation of sequence co...

Page 32: ...ot exceed 10 units The total cable length must not exceed 200m see S1 X11 for examples for connection of MotorControllers A slave can only have one master whereas a master can have several slaves and a MotorController can both be a slave and a master to MotorControllers Configuration of Master Slave system A connected slave MotorController is shown on the master MotorController s touch screen When...

Page 33: ... menus on the touch screen can be viewed but no values can be changed Chosen persons with a special key 3 Configuration You can open the MotorController and operate the touch screen for showing status manual operating of the windows as well as configuration and changing the pre set values All the menus and sub menus can be seen and the values can be changed Access Level 3 can be locked with a PIN ...

Page 34: ...ee appendix for detailed explanation It is possible to lock the touch screen before the time has expired press followed by pressing Configuration files on USB The MotorController has a plug in for an USB stick It is possible to save all the configurations of the MotorController and this way save the stick as documentation It is also possible to reinstall from the USB stick Files on the USB stick c...

Page 35: ...mounted a set of KNX or BACnet objects are available for each motor line and motor group which provides the options for status and commands Status objects E g actual position fault and operation status and the max opening angle degrees Command objects E g target position commands with different priority and MotorLink motor speed Fieldbus link Conn 1 10 The KNX or BACnet has also 10 configurable bi...

Page 36: ...ual position COV increment 4 Actual max position COV increment 5 High speed COV increment 6 Wind direction COV increment 7 Register as foreign device 13 Status main menu In Status you can see the status of all the menu items that can be configured under Configuration as well as e g the status of the power supply and slots inform the type of card in the slot Main overview status of the system Under...

Page 37: ...d here If you are logged into access level 3 it is also possible to configure from this menu 16 Hardware error main menu If there are any hardware error on the MotorController they will be displayed here E g if the motor lines are not configured the main supply is cut of the type of weather station is not selected etc If you are logged into access level 3 it is also possible to configure from this...

Page 38: ...of the MotorController it is necessary to allow remote control This is done in the configuration of the system Identification of the IP address IP address of the MotorController Screen shot from the PC when controlling the FlexiSmoke remotely Start the WMaFlexiSmokeRemote program on the connected PC Enter the IP address and press Connect 19 Commissioning and test run In case of hardware error plea...

Page 39: ...in our factory Only install original spare parts We recommend that the software of the MotorController is updated during the annual maintenance check The expected minimum lifetime for the MotorController is 10 years Maintenance agreements WindowMaster offer maintenance agreements for the MotorController Contact our service department for further information telephone 44 1536 510990 or info windowm...

Reviews: