4 - 45
4 Basic Operation
E5@C Digital Temperature Controllers User’s Manual (H174)
4-1
2 Usin
g Heater Burn
ou
t (H
B) an
d He
ater Sho
rt (HS)
Alarms (Not
Su
pp
or
ted
f
o
r P
o
sitio
n
-p
ro
p
o
rt
io
nal Mo
dels.)
4
4-12-4 C
alculating
Detection
Current V
a
lues
Calculate the set value using the following equation:
• To set the current for heater burnout when two or more heaters are connected through the CT, use
the value from when the heater with the smallest current burns out. If all of the heaters have the same
current, use the value from when any one of them burns out.
Example: Set value of Heater Burnout Detection 1 or 2 parameter = (Normal current value
×
Number
of loops + Burnout current value)/2
• Make sure that the following conditions are satisfied:
Heater with a current of less than 10.0 A:
(Normal current value)
−
(Burnout current value)
≥
1 A
When the difference is less than 1 A, detection is unstable.
Heater with a current of 10.0 A or more:
(Normal current value)
−
(Burnout current value)
≥
2.5 A
When the difference is less than 2.5 A, detection is unstable.
• The setting range is 0.1 to 49.9 A. Heater burnouts and heater shorts are not detected when the set
value is 0.0 or 50.0. When the set value is 0.0, the HB alarm is always OFF and the HS alarm is
always ON. When the set value is 50.0, the HB alarm is always ON and the HS alarm is always OFF.
• Set the total current value for normal heater operation to 50 A or less. When a current value of 55.0 A
is exceeded,
ffff
is displayed in the Heater Current 1 (or 2) Value Monitor and Leakage Current 1
(or 2) Monitor parameters.
(1) Single-phase Heaters
Example: Using a 200-VAC, 1-kW Heater
The heater power supply provides 5 A when the current is normal, and 0 A when there is a
burnout, so the heater burnout detection current is calculated as follows:
4-12-4 Calculating Detection Current Values
4-12-5 Application Examples
Normal
Burnout
Heater Burnout Detection 1/2 set value = Normal current value + Burnout current value
2
HS Alarm 1/2 set value = Leakage current value (output OFF) + HS current value
2
CT
5 A
5 A
Load
AC line
200 V
Product
To CT input
CT
0 A
Load
Load (such as a heater)
AC line
Burnout
200 V
Product
To CT input
Heater burnout detection current =
(Normal current) + (Heater burnout current)
2
=
5 + 0
2
= 2.5 [A]
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...