6-3 Op
er
a
tion
Le
v
el
6
a-m
Auto/Manual Switch
The Event Input Assignment 1 to Event Input
Assignment 6 parameters must not be set to Auto/
Manual and the Auto/Manual Select Addition
parameter must be set to ON. The control must be
set to 2-PID control.
• This parameter switches the Controller between Automatic and Manual Modes.
• If the
O
Key is pressed for at least 3 seconds when the Auto/Manual Switch parameter is
displayed, the Manual Mode will be entered and the manual control level will be displayed.
• This parameter will not be displayed if an event input is set to "MANU" (auto/manual).
z
Related Parameters
PID ON/OFF (Initial Setting Level): Page 6-44
Auto/Manual Select Addition (Advanced Function Setting Level): Page 6-72
m-sp
Multi-SP Set Point Selection
(Set Points 0 to 7)
The Number of Multi-SP Points parameter must not
be set to OFF and the Event Input Assignment 1 to
Event Input Assignment 6 parameters must not be
set to “Multi-SP No. switching bit 0” to “Multi-SP
No. switching bit 2.”
To use the multi-SP function, preset the eight set points (SP 0 to 7) in the Adjustment Level,
and then switch the set point either by operating the keys or by using external input signals
(event inputs).
This parameter is used to select set points 0 to 7.
rsp
Remote SP Monitor
There must be a remote SP input.
The ST parameter must be set to OFF.
The Remote SP Enable parameter must be set to
ON.
This parameter is used to monitor the remote SP.
z
Related Parameters
SP Mode (Adjustment Level): Page 6-21
Remote SP Enable (Advanced Function Setting Level): Page 6-81
Remote SP Upper Limit (Advanced Function Setting Level): Page 6-82
Remote SP Lower Limit (Advanced Function Setting Level): Page 6-82
Operation
See
See
Function
000
Monitor
Monitor range
Unit
Remote SP lower limit
−
10% to Remote SP upper limit +10%
EU
See
See
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...