A - 33
A Appendices
E5@C Digital Temperature Controllers User’s Manual (H174)
A
-6 P
aram
eter Operation L
ists
A
A-6-9 Initialization Accordin
g to P
a
rameter C
hanges
*9
For a temperature input, the Integral/Derivative Time Unit parameter is initialized only when the RT parameter is turned
ON. The default is as follows:
•
Integral/Derivative Time Unit: 0.1 s (The PID parameters are also initialized when the Integral/Derivative Time Unit
parameter is initialized.)
*19
*10
This parameter is initialized to the new Password to Move to Protect Level password.
*11
When the ST parameter is turned ON, the SP Mode parameter is initialized to LSP and the Remote SP Enable
parameter is initialized to OFF.
*12
When the Remote SP Enable parameter is turned OFF, the SP Mode parameter is initialized to LSP.
*13
These parameters are initialized when the Input Type parameter is changed from a temperature input to an analog input
or from an analog input to a temperature input.
*14
This parameter is initialized when the Input Type parameter is changed from a temperature input to an analog input or
from an analog input to a temperature input. However, it is not initialized if the applicable alarm is an MV absolute-value
upper-limit alarm or an MV absolute-value lower-limit alarm.
*15
This parameter is initialized to 50 (0.50%) if a non-MV alarm is changed to an MV alarm. This parameter is initialized to
2 (0.2
°
C or 0.02%FS) if an MV alarm is changed to a non-MV alarm.
*16
Write to both so that the SP and the currently selected Multi-SP SP0 to SP7 match.
*17
When the ST condition is met, the SP Mode parameter is initialized to LSP and the Remote SP Enable parameter is
initialized to OFF.
*18
Initialized to 0.8 when the temperature unit is
°
C, and to 1.4 when the temperature unit is
°
F.
*19
These parameters are initialized as follows:
•
Integral/Derivative Time Unit of 1 s: Proportional band to 8, integral time to 233, and derivative time to 40. (This
applies to both the heating and cooling constants.)
•
Integral/Derivative Time Unit of 0.1 s: Proportional band to 8.0, integral time to 233.0, and derivative time to 40.0.
(This applies to both the heating and cooling constants.)
*20
This parameter is initialized to 4.0 for closed control and 2.0 for floating control.
*21
If the Close/Floating parameter is set to floating and the integral time is 0, the parameter is initialized to 233. If the
integral time is 0.0, it is initialized to 233.0.
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...