![background image](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592151.webp)
5 - 3
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-1 Sh
iftin
g
In
pu
t V
a
lue
s
5
5-1
Shifting Input Values
z
Shifting Inputs
You can set the Process Value Slope Coefficient and Process Value Input Shift parameters to
compensate the PV.
• Calculating the Process Value Slope Coefficient and Process Value Input Shift
In the following equation, PVi is the input to the calculation, PVo is the result, INRT is the process
value slope coefficient, and INS is the process value input shift: PVo = (PVi
×
INRT) + INS
z
Moving Average
• The moving average operation reduces sudden changes in the input due to noise and other
factors, and can be enabled separately for each input.
• The Moving Average Count parameter is used for the moving average. It can be set to OFF, 2, 4,
8, 16, or 32.
• The default is OFF (disabled).
*
The default is 8 for models other than the E5
@
C-
@
-0
@
.
Parameter
Setting range
Unit
Default
Process Value Input Shift
Temperature input:
−
199.9 to 999.9
°
C or
°
F
0.0
Analog input:
−
1,999 to 9,999
EU
0
Process Value Slope Coefficient
0.001 to 9.999
None
1.000
Parameter
Setting range
Unit
Default
Moving Average Count
OFF, 2, 4, 8, 16, or 32
Times
OFF*
000
Input data
Operation result
Time
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...