5 - 19
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-7 Usin
g th
e K
e
y Pr
otec
t Le
v
e
l
5
5-7-1 Protection
5-7
Using the Key Protect Level
• To move to the Protect Level, press the
O
and
M
Keys simultaneously for at least three seconds in
Operation Level or Adjustment Level.*
* The key pressing time can be changed in the Move to Protect Level Time parameter (Advanced Function
Setting Level).
• The Protect Level protects parameters that are not changed during Controller operation until
operation is started to prevent them from being modified unintentionally.
There are four types of protection: operation/adjustment protect, initial setting/communications
protect, setting change protect, and PF Key protect.
• The protect level settings restrict the range of parameters that can be used.
z
Operation/Adjustment Protect
The following table shows the relationship between set values and the range of protection.
z
Initial Setting/Communications Protect
This protect level restricts movement to the Initial Setting Level, Communications Setting Level, and
Advanced Function Setting Level.
5-7-1
Protection
• Parameters are not protected when the set value is set to 0.
• The default is 0.
• The default is 1.
0
oapt
Level
Set value
0
1
2
3
Operation
Level
PV
Can be dis-
played
Can be dis-
played
Can be dis-
played
Can be dis-
played
PV/SP
Can be dis-
played and
changed
Can be dis-
played and
changed
Can be dis-
played and
changed
Can be dis-
played
Others
Can be dis-
played and
changed
Can be dis-
played and
changed
Cannot be dis-
played and
moving to
other levels is
not possible
Cannot be dis-
played and
moving to
other levels is
not possible
Adjustment Level
Can be dis-
played and
changed
Cannot be dis-
played and
moving to
other levels is
not possible
Cannot be dis-
played and
moving to
other levels is
not possible
Cannot be dis-
played and
moving to
other levels is
not possible
1
icpt
Set value
Initial Setting Level
Communications
Setting Level
Advanced Function
Setting Level
0
Possible to reach
Possible to reach
Possible to reach
1
Possible to reach
Possible to reach
Not possible to reach
2
Not possible to reach
Not possible to reach
Not possible to reach
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...