6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6
-7 In
itial Set
ting
Le
v
e
l
6
6-7
Initial Setting Level
This level is used to set up the basic Digital Controller specifications. In this level, you can set the Input
Type parameter to set the sensor input to be connected, limit the setting range of set points, set the
alarm modes, and perform other operations.
To move from the Operation Level to the Initial Set-
ting Level, press the
O
Key for at least three sec-
onds with any parameter displayed except for the
Auto/Manual Switch parameter.
• The Initial Setting Level is not displayed when the
Initial Setting/Communications Protect parameter
is set to 2. It can be used when the Initial
Setting/Communications Protect parameter is set
to 0 or 1.
• If the Input Type parameter is set for an analog
input, the following parameters will be set: Scaling
upper limit, Scaling lower limit, and Decimal point.
25
100
Operation
Level
Initial Setting
Level
Control stops.
Control in progress
Control stopped
Press the
O
Key for at
least 1 s; display will flash.
Press the
O
Key
for at least 3 s.
Power ON
Press the
O
Key
for at
least 1 s.
M
20
cp
M
s
in-t
M
100
in-h
M
0
in-l
M
0
dp
M
c
d-u
M
1300
sl-h
M
-200
sl-l
M
onof
cntl
M
stnd
s-hc
M
on
st
M
off
ptrn
M
M
or-r
orev
M
2
alt1
M
0.2
alh1
M
2
alt2
M
0.2
alh2
M
2
alt3
M
0.2
alh3
M
2
alt4
M
0.2
alh4
M
4-20
o1st
M
4-20
o2st
M
M
M
100.0
tr-h
M
0.0
tr-l
M
msp0
ev-1
M
stop
ev-2
M
none
ev-3
M
none
ev-4
M
none
ev-5
M
none
ev-6
M
flo
t
clfl
M
off
calb
M
20
c-cp
M
off
tr-t
4-20
trst
M
30
mot
off
sqr
0
amov
Move to Advanced
Function Setting
Level
ST
Event Input
Assignment 1
Event Input
Assignment 2
Event Input
Assignment 3
Event Input
Assignment 4
Event Input
Assignment 5
Event Input
Assignment 6
Initial Setting Level
Page
Page
Input Type
Scaling Upper
Limit
Scaling Lower
Limit
Decimal Point
Temperature Unit
SP Upper Limit
SP Lower Limit
PID·ON/OFF
Program Pattern
Control
Period (Heating)
Control Period
(Cooling)
Direct/Reverse
Operation
Alarm 1 Type
Alarm 2 Type
Alarm 3 Type
Transfer Output
Type
Transfer Output
Upper Limit
Transfer Output
Lower Limit
Standard or
Heating/Cooling
Alarm 1
Hysteresis
Alarm 2
Hysteresis
Alarm 3
Hysteresis
Extraction of
Square Root
Enable
Page
Alarm 4 Type
Alarm 4
Hysteresis
Control Output 1
Signal
Control Output 2
Signal
Transfer Output
Signal
Close/Floating
Motor Calibration
Travel Time
000
000
000
000
000
000
000
000
000
6-42
6-43
6-43
6-43
6-43
6-44
6-44
6-44
6-45
6-45
6-46
6-46
6-46
6-47
6-47
6-51
6-47
6-51
6-47
6-51
6-47
6-51
6-52
6-52
6-53
6-52
6-54
6-54
6-55
6-55
6-55
6-55
6-55
6-55
6-58
6-58
6-57
6-57
6-58
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...