![Omron E5C series User Manual Download Page 306](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592306.webp)
6 Parameters
6 - 90
E5@C Digital Temperature Controllers User’s Manual (H174)
svst
SV Status Display Function
• This parameter sets a control or alarm status that is displayed alternately in 0.5-s cycles
on the No. 2 display when the PV is set to be displayed in the No. 1 display.
• PV
• PV/SP*
• PV/Manual MV (Valve Opening)
• PV/SP/Manual MV (Valve Opening)
*
This includes when the PV/SP is selected for the Monitor/Setting Item parameter.
z
Related Parameters
Process Value/Set Point (Operation Level): Page 6-8
PV/MV (Manual MV) (Manual Control Level): Page 6-40
d.ref
Display Refresh Period
• This parameter delays the display refresh period for monitor values. Only display
refreshing is delayed, and the refresh period for process values used in control is not
changed.
• This function is disabled by setting the parameter to OFF.
Function
Setting
Setting range
Default
off
:
No SV status display
off
manu
:
MANU is alternately displayed during manual control.
stop
:
STOP is alternately displayed while operation is stopped.
alm1
:
ALM1 is alternately displayed during Alarm 1 status.
alm2
:
ALM2 is alternately displayed during Alarm 2 status.
alm3
:
ALM3 is alternately displayed during Alarm 3 status.
alm4
:
ALM4 is alternately displayed during Alarm 4 status.
alm
:
ALM is alternately displayed when Alarm 1, 2, 3, or 4 is set to ON.
ha
:
HA is alternately displayed when an HB alarm or HS alarm is ON.
See
See
Function
Setting
Setting range
Unit
Default
OFF, 0.25, 0.5, 1.0
Seconds
0.25
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...