4 Basic Operation
4 - 16
E5@C Digital Temperature Controllers User’s Manual (H174)
• Function assignments can be changed by changing the settings for control and auxiliary output
assignments.
• The default function assignments for each output are shown below.
*
If the Controller is equipped with HB/HS alarm detection, it is set by default to detect heater alarms (HA).
Therefore, the alarm 1 function is disabled and the Alarm 1 Type is not displayed. To enable alarm 1, set an
output assignment to alarm 1. If the Program Pattern parameter is changed to a setting other than OFF,
Auxiliary Output 1 Assignment parameter is set as the program end output.
• Refer to page 6-79 for the functions that can be assigned to the outputs.
• Each output is automatically initialized as shown below by changing the control mode between
standard and heating/cooling.
In this example, direct/reverse operation, and control period
(heating) parameters are checked.
Direct/reverse operation =
or-r
(reverse operation)
Control period (heating) = 20 (seconds)
Operating Procedure
• Setting the Control Period (Heating) Parameter
1
Press the
M
Key several times in the Initial Setting Level to
display
cp
(Control Period (Heating)).
Initial Setting Level
2
Press the
U
or
D
Key to set the value to 20.
The default for a relay output is 20 seconds.
• Setting Direct/Reverse Operation
1
Press the
M
Key several times in the Initial Setting Level to
display
orev
(Direct/Reverse Operation).
Initial Setting Level
2
Press the
U
or
D
Key to select
or-r
(Reverse Operation).
The default is
or-r
(Reverse Operation).
4-6-3
Assigned Output Functions (Assigning Control Outputs Is Not
Supported for Position-proportional Models.)
Parameter name
Display
Initial status
Control Output 1 Assignment
out1
Control output
(heating)
Control Output 2 Assignment
out2
Not assigned.
Auxiliary Output 1 Assignment
sub1
Alarm 1*
Auxiliary Output 2 Assignment
sub2
Alarm 2
Auxiliary Output 3 Assignment
(E5CC/E5EC/E5AC only)
sub3
Alarm 3
Auxiliary Output 4 Assignment
(E5EC/E5AC only)
sub4
Alarm 4
20
cp
Control Period
(Heating)
20
cp
or-r
orev
Direct/Reverse
Operation
or-r
orev
Summary of Contents for E5C series
Page 2: ......
Page 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Page 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Page 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...