8. HOW TO USE INDEXER
8 - 6
(2) Other parameter settings
(a) Setting assignment direction of station No.
Select an assignment direction of station No. with [Pr. PA14].
CW
CCW
[Pr. PA14] setting
Assignment direction of station No.
0
Next station No. will be assigned in CW direction in order of
1, 2, 3…
1
Next station No. will be assigned in CCW direction in order
of 1, 2, 3…
Station No.
1
2
3
4
CW direction
Station No.
1 2
3 4
CCW direction
[Pr. PA14]: 0 (initial value)
[Pr. PA14]: 1
(b) Setting number of stations
Set a number of stations to [Pr. PT28].
[Pr. PT28] setting value
Number of stations
2
3
4
255
Station No.
No. 0
No. 1
No. 2
No. 1
No. 0
No. 3
No. 0
No. 1
No. 2
No. 0 No. 254
No. 1
(3) Operation
Selecting the next station with "Target point table" and switching on "Controlword bit 4 (New set-point)"
starts positioning to the selected next station at the set speed, acceleration time constant and
deceleration time constant.
Item
Object/register to be used
Setting
Rotation direction selection
Controlword
Set the rotation direction in "Controlword bit 5 (Direction)".
The setting is shown as follows:
Off: Station No. decreasing direction
On: Station No. increasing direction
Station No. selection
Target point table
Set a station No. at which positioning starts.
Start
Controlword
Switch on "Controlword bit 4 (New set-point)".
Summary of Contents for MR-JE-C
Page 33: ...2 SIGNALS AND WIRING 2 16 MEMO ...
Page 37: ...3 STARTUP 3 4 MEMO ...
Page 129: ...6 HOMING MODE 6 36 MEMO ...
Page 169: ...7 HOW TO USE THE POINT TABLE 7 40 MEMO ...
Page 203: ...9 HOW TO USE JOG MODE 9 12 MEMO ...
Page 215: ...11 APPLICATION OF FUNCTIONS 11 8 MEMO ...
Page 307: ...12 WHEN USING WITH A GENERAL PURPOSE INTERFACE 12 92 MEMO ...
Page 309: ...MEMO ...