10. OBJECT DICTIONARY
10 - 37
10.4.8 Touch probe (60B8h to 60BBh)
POINT
The touch probe function cannot be used in the indexer method.
The current position latch data at the time of TPR1 (Touch probe 1) and TPR2 (Touch probe 2) input can be
read.
(1) Object list
Index
Sub
Index
Name Data
Type
Access
60B8h
0
Touch probe function
U16
rw
60B9h
0
Touch probe status
U16
ro
60BAh
0
Touch probe pos1 pos value
I32
ro
60BBh
0
Touch probe pos1 neg value
I32
ro
60BCh
0
Touch probe pos2 pos value
I32
ro
60BDh
0
Touch probe pos2 neg value
I32
ro
When the touch probe function (60B8h) is set, and TPR1 (Touch probe 1) and TRP2 (Touch probe 2),
external signals, are turned on/off, the current position of the rising and falling edges are latched.
The latch status of the current position data can be checked with Touch probe status (60B9h). The
latched current data can be read with Touch probe pos1 pos value (60BAh) and Touch probe pos1 neg
value (60BBh). The following shows the touch probe detection resolution. Enabling the high precision
touch probe disables the encoder output pulses. For details of each object, refer to sections 10.4.9 to
10.4.14.
Touch probe1
Touch probe2
Input terminal
TPR1 TPR2
Encoder
resolution
[Pr. PD37] = _ _ _ 0 (Selection of high-precision touch
probe is disabled)
55 µs
55 µs
[Pr. PD37] = _ _ _ 1 (Selection of high-precision touch
probe is enabled)
55 µs
Rising edge: 2 µs
Falling edge: 55 µs