4. STARTUP
4 - 3
4.2 Startup
Confirm that the servo motor operates properly alone before connecting the servo motor with a machine.
(1) Slide switch setting
To switch to CC-Link IE Field Network Basic communication, turn the slide switch 1 (SW1-1) "OFF
(down)" and turn the slide switch 2 (SW1-2) "ON (up)".
(2) Power on
When the main and control circuit power supplies are turned on, "b01" (when the identification number is
"01h") appears on the servo amplifier display.
When the absolute position detection system is used in a rotary servo motor, [AL. 25 Absolute position
erased] occurs with first power on, and the servo-on status cannot be made. Cycle the power to
deactivate the alarm.
If the power is switched on when the servo motor is rotated by an external force at a speed of 3000 r/min
or higher, it may cause a position mismatch. Make sure that the servo motor is not rotated before
switching the power on.
(3) IP address setting
POINT
Use a twisted pair cable with Ethernet Category 5e (1000BASE-T) or higher as
an Ethernet cable. The maximum cable length between nodes is 100 m.
Use a hub with a transmission speed of 100 Mbps or faster when branching the
Ethernet communication using a switching hub.
For the switching hub without the auto-negotiation function, set it to the
transmission speed of 100 Mbps and half duplex.
The initial value of the IP address is 192.168.3.0.
The 4th octet can be set to 1 to 255 by using rotary switches (SW2/SW3).
Cycle the power of the servo amplifier after changing the parameter setting of
the IP address or using the rotary switches (SW2/SW3).
The IP address range of CC-Link IE Field Network Basic is between 0.0.0.0 and
223.255.255.254. Set the IP address within the range.