4. STARTUP
4 - 18
4.6.2 Cyclic communication start
Start the cyclic communication in the following procedure.
Network setting
[IP address setting]
The initial value is 192.168.3.0. To change the initial value, set it with any of the following
(1) to (3). (Refer to section 4.2 (3).)
(1) Rotary switches (SW2/SW3)
(2) Parameters ([Pr. PN11] to [Pr. PN12])
(3) SLMP communication (IP Address Set command)
[Subnet mask setting]
The initial value is 255.255.255.0. To change the initial value, set it with either of the
following (1) or (2). (Refer to chapter 7.)
(1) Parameters ([Pr. PN13] to [Pr. PN14])
(2) SLMP communication (IP Address Set command)
[Slave station (servo amplifier) power cycling]
The settings of the IP address and subnet mask are reflected.
Communication start
procedure
[Cyclic communication start]
Start the cyclic communication of the master station (controller).
[Cyclic communication ready]
Set RY (n + 3) F of the master station (controller) to "01h". For the slave stations (servo
amplifiers), start importing the word device (RWw) and set RX (n + 3) F to "01h".
For the master station (controller), check that RX (n + 3) F is "01h" and read the word
device (RWr).
IP address setting
Slave station (servo amplifier)
power cycling
Cyclic communication ready
Master station (controller) cyclic
communication start
Subnet mask setting