80070101-2c01ffff
Sensor [SensorElementName] has transitioned from normal to non-critical state. (ML2
OverTemp)
Explanation:
This message is for the use case when an implementation has detected a Sensor transitioned to
non-critical from normal.
May also be shown as 800701012c01ffff or 0x800701012c01ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0520
SNMP Trap ID:
12
Automatically notify Support:
No
User response:
1.
Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear of the server),
that the air baffle is in place and correctly installed, and that the server cover is installed and completely closed.
2.
Check the ambient temperature. You must be operating within the specifications (see Server Features and
specifications for more information).
3.
Replace the failed ML2 card.
8007010d-2582ffff
Sensor [SensorElementName] has transitioned from normal to non-critical state. (RAID Vol
State)
Explanation:
This message is for the use case when an implementation has detected a Sensor transitioned to
non-critical from normal.
May also be shown as 8007010d2582ffff or 0x8007010d2582ffff
Severity:
Warning
Alert Category:
Warning - Other
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0520
SNMP Trap ID:
60
Automatically notify Support:
No
User response:
1.
Run the hard disk drive diagnostic test on drive n.
2.
Reseat the following components: a. Hard disk drive (wait 1 minute or more before reinstalling the drive) b.
Cable from the system board to the backplane
3.
Replace the following components one at a time, in the order shown, restarting the server each time: a. Hard
disk drive b. Cable from the system board to the backplane c. Hard disk drive backplane (n = hard disk drive
number)
80070101-2c01ffff • 8007010d-2582ffff
Appendix A. Integrated management module II (IMM2) error messages
397
Summary of Contents for System x3650 M5
Page 1: ...System x3650 M5 Type 5462 Installation and Service Guide ...
Page 2: ......
Page 3: ...System x3650 M5 Type 5462 Installation and Service Guide ...
Page 8: ...vi System x3650 M5 Type 5462 Installation and Service Guide ...
Page 16: ...xiv System x3650 M5 Type 5462 Installation and Service Guide ...
Page 58: ...42 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 86: ...70 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 320: ...304 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 832: ...816 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 988: ...972 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 992: ...976 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 1001: ...Taiwan Class A compliance statement Notices 985 ...
Page 1002: ...986 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 1008: ...992 System x3650 M5 Type 5462 Installation and Service Guide ...
Page 1009: ......
Page 1010: ... Part Number 00AK781 Printed in USA 1P P N 00AK781 ...