![Fuji Electric FRENIC-Ace series User Manual Download Page 776](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846776.webp)
Appendix G Conformity with Standards
Appendix-36
Power supply
voltage
Nominal applied
motor
(kW)
Inverter type
ND/HD/HND
mode
MCCB or RCD/ELCB *1
Rated current
W/DCR
W/o DCR
Single-phase
200 V
0.1
FRN0001E2
■
-7
HHD
5
5
0.2
FRN0002E2
■
-7
HHD
5
5
0.4
FRN0003E2
■
-7
HHD
5
10
0.75
FRN0005E2
■
-7
HHD
10
15
1.5
FRN0008E2
■
-7
HHD
15
20
2.2
FRN0011E2
■
-7
HHD
20
30
Note: A box (
■
) in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the
enclosure.
A box (
) in the above table replaces GA, GB or C depending on the model.
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, depending
on the power transformer capacity. Refer to the related technical documentation for details.
5. The inverter should be used in an environment that does not exceed Pollution Degree 2 requirements. If the
environment has a Pollution Degree 3 or 4, install the inverter in an enclosure of IP54 or higher.
6. Install the inverter, AC or DC reactor, input or output filter in an enclosure with minimum degree of protection
of IP2X (Top surface of enclosure shall be minimum IP4X when it can be easily accessed), to prevent human
body from touching directly to live parts of these equipment.
7. Do not connect any copper wire directly to grounding terminals. Use crimp terminals with tin or equivalent
plating to connect them.
8. When you use an inverter at an altitude of more than 2000 m, you should apply basic insulation for the
control circuits of the inverter. The inverter cannot be used at altitudes of more than 3000 m.
9. Use wires described in Chapter 2 “2.2.5 [ 1 ] Screw specifications” and “2.2.5 [ 3 ] Recommended wire size
(main circuit terminals).”
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......