9.2 CANopen Communication
9-42
9.2.11 Heartbeat and Node Guarding
The Heartbeat and Node Guarding services are provided for detecting disconnection. We recommend you to use
either one.
Important: The use of either Heartbeat or Node Guarding is recommended
The setting for detecting disconnection in the CANopen device is invalid by default. Unless the setting is
enabled, the CANopen network including inverter can not detect a disconnection even if the disconnection
occurs. We strongly recommend to enable the setting.
[ 1 ] Heartbeat
Heartbeat is a mechanism to detect the disconnection in the CANopen network by monitoring the signals from the
specified node.
For more information about detailed behavior of Heartbeat, refer to the CANopen specifications DS 301.
Do not use both Heartbeat and Node Guarding at the same time. If they are used at the same time, the
disconnection is not detected properly. To use Heartbeat, make Node Guarding invalid, that is, set Index
100C=0 and Index 100D=0 (refer to Section 9.2.11 [ 2 ] ).
(1) Related object list
Index
(Hex)
Sub
Name
Description
Data type
Access
1016
-
Consumer heartbeat time
ARRAY
-
0
Number of entries
Number of configurations: 1
UNSIGNED8
R
1
Consumer heartbeat time
Upper word: Node ID to be monitored
Lower word: Heartbeat monitoring time
Default value: 0 (no operation)
UNSIGNED32
RW
1017
-
Producer heartbeat time
Transmission cycle of Heartbeat message
Default value: 0 (no operation)
UNSIGNED16
RW
(2) Consumer heartbeat time
It is the preset time interval within the Heartbeat signals should be received from the specified node ID (Heartbeat
producer). The behavior is as follows: if the Heartbeat signal can not be received over monitoring time, the
disconnection is deemed to occur.
For information on the behavior upon the CANopen disconnection, refer to “9.2.12 Behavior upon detection
of CANopen network disconnection”.
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
0000
Node ID to be monitored
Heartbeat monitoring time (ms)
(3) Producer Heartbeat time
Automatically transmits the Heartbeat signals continuously at the preset interval (on a 1 ms basis). Another node
(Heartbeat consumer) monitors this Heartbeat signals.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......