5.3 Description of Function Codes
5-121
FU
NCT
IO
N
C
O
DE
S
Chap 5
■
Pattern operation stage No. 1 – “STG1” (Function code data = 18), Pattern operation stage No. 2 –
“STG2” (Function code data = 19), Pattern operation stage No. 4 – “STG4” (Function code data = 20)
Outputs the stage (operation process) currently performed during pattern operation.
Operation pattern stage No.
Output terminal signal
STG1
STG2
STG4
Stage 1
ON
OFF
OFF
Stage 2
OFF
ON
OFF
Stage 3
ON
ON
OFF
Stage 4
OFF
OFF
ON
Stage 5
ON
OFF
ON
Stage 6
OFF
ON
ON
Stage 7
ON
ON
ON
■
Frequency (speed) arrival 2 – “FAR2” (Function code data = 21)
The signals come ON when the difference between the output frequency before torque limiting and reference
frequency is within the frequency arrival hysteresis width specified by E30 and the frequency arrival delay specified
by E29 has elapsed. (
Function codes E29 and E30)
■
Cooling fan in operation – “FAN” (Function code data = 25)
With the cooling fan ON/OFF control enabled (H06 = 1), this output signal is ON when the cooling fan is in
operation, and OFF when it is stopped. This signal can be used to make the cooling system of peripheral
equipment interlocked for an ON/OFF control. (
Function code H06)
■
Auto-resetting – “TRY” (Function code data = 26)
This output signal comes ON when auto resetting (resetting alarms automatically) is in progress.
(
Function codes H04 and H05)
■
Universal DO -- “U-DO” (Function code data = 27)
Assigning this output signal to an inverter's output terminal and connecting the terminal to a digital input terminal of
peripheral equipment, allows an upper controller to send commands to the peripheral equipment via the RS-485 or
the fieldbus communications link. The universal DO can be used as an output signal independent of the inverter
operation.
For the procedure for access to Universal DO via the RS-485 or fieldbus communications link, refer to the
respective instruction manual.
■
Heat sink overheat early warning – “OH” (Function code data = 28)
This output signal is used to issue a heat sink overheat early warning that enables you to take a corrective action
before an overheat trip
0h1
actually happens.
ON at [(Overheat trip (
0h1
) temperature) – 5°C (41°F)] or higher
OFF at [(Overheat trip (
0h1
) temperature) - 8°C (46°F)] or lower
This signal comes ON also when the internal air circulation DC fan (FRN0203 E2
-4
or above for 400 V class
series) is locked.
■
Synchronization completed -- “SY” (Function code data = 29)
This output signal comes ON when the control target comes inside the synchronization completion detection angle
in synchronous running.
For details about master-follower operation, refer to function codes J73 to J88.
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......