9.1 Overview of RS-485 Communication
9-1
CO
M
M
U
NI
C
AT
IO
N
FUN
CT
IO
N
S
Chap 9
9.1 Overview of RS-485 Communication
The FRENIC-Ace has two RS-485 communication ports at the locations shown below.
(i)
Communication port 1: RJ-45 connector for the keypad (modular jack)
(ii) Communication port 2:
RJ-45 connector for RS-485 communication (modular jack) * only for type FRN-E2
■
-2/4/7GA, -2/4/7J;
RS-485 terminals (control circuit terminals SD, DX-, DX+) * only for FRN-E2
■
-2/4/7GB, -4C
COM port 1
COM port 2
Using the RS-485 communication ports shown above enables the extended functions listed below.
•
Remote operation from a keypad at the remote location (COM port 1)
The standard keypad enables remote operation by mounting the keypad on a remote panel and connecting the
keypad to RJ-45 connector with an extension cable. (maximum cable length: 20 m)
•
Operation by FRENIC Loader (COM ports 1 and 2)
It is possible to edit and monitor the function codes by connecting the RJ-45 connector (RS-485 communication)
in the inverter and PC and using the inverter support loader (FRENIC Loader, see “9.3 FRENIC Loader
Overview”).
•
Control via host equipment (COM ports 1 and 2)
Connecting the inverter to the host equipment (upper controller), such as a computer and programmable
controller (PLC), enables to control the inverter as a subordinate device.
Besides the communication port 1 (RJ-45 connector) shared with the keypad, the FRENIC-Ace has the RS-485
communication port 2 by default.
The protocols for controlling inverters support the Modbus RTU protocol (compliant to the protocol established
by Modicon Inc.) that is widely used and the Fuji Electric’s general-purpose inverter protocol that is common to
Fuji Electric’s inverters including conventional series.
•
Connecting the keypad to the COM port 1 automatically switches to the keypad protocol; there is no
need to modify the function code setting.
•
When using FRENIC Loader, which requires a special protocol for handling Loader commands, you
need to set up some communication function codes accordingly.
For details, refer to the FRENIC Loader Instruction Manual.
For details of RS-485 communication, refer to the RS-485 Communication User’s Manual.
RJ-45
connector
RJ-45
connector
RS-485 terminals (SD, DX-, and DX+)
(which facilitate multi-drop connection.)
Summary of Contents for FRENIC-Ace series
Page 20: ......
Page 32: ......
Page 92: ......
Page 94: ......
Page 452: ......
Page 490: ......
Page 504: ......
Page 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Page 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Page 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Page 582: ......
Page 664: ...11 15 External Cooling Fan Attachments 11 60...
Page 690: ......
Page 692: ......
Page 720: ......
Page 738: ......
Page 787: ......